8.
Connect
the
electrical
supply
to the
water
heater.
NOTE: Remove the standard 1/2 inch knock-out (opening)
in the junction box for conduit connections.
9.
Connect ground wire to green ground wire in the electrical
junction box of the water heater.
10. Reinstall the junction box cover.
11. Reattach
the left touvered access panel
to the water
heater and secure it using the screws loosened earlier.
12. Turn on electrical power to the water heater.
13. Press the power button to turn the water heater on, then
press the Efficiency
button to set the operating
mode.
NOTE: The water heater wilt conduct a system diagnostic
(approximately
8 minutes) prior to operation.
14. Once
the
diagnostic
sequence
has
finished,
the
fan
should
turn
on
followed
by
the
compressor.
NOTE: The heat pump's fan wilt not turn on if the incoming
water temperature
is tess than 59 °F and/or the ambient
air temperature is above 109 °F or below 45 °F. Should the
internal diagnostics detect a problem with the heat pump,
an error message will be displayed.
15. Set the operational
mode. For typical
installation,
the
Hybrid Mode offers the best combination
of efficiency
and hot water delivery. For detailed descriptions
of all
operational
modes see "Adjusting
the User
Interface
Module/Operational
Modes" section.
Green
Ground
Wire
Ground
Wire
Red Wire
Conduit
(Field Connection)
FIGURE 13.
Wiring Diagram
• Before
removing
any access
panels or servicing
the water
heater, make sure the electrical
supply to the water heater is
turned "OFF".
• Failure to do this could result in
death, serious bodily injury, or
property damage.
Connecting
the Condensate
Pump
Overflow
Shut Off Switch
Condensate
Pump Shut-off Switch Wiring Loop
18 AWG - White
(Loop Located Behind Junction Box)
!
White Wires
From Water Heater
Wires to Condensate
Pump Overflow
Shut Off Switch
(18 AWG or Larger)
FIGURE 15.
1.
Turn off power to the electrical wiring for the water heater
at the circuit breaker/fuse box.
2.
Locate the white 18 AWG wire loop behind the field wiring
junction box. See Figure 15.
3.
Cut the loop and strip insulation off of the two ends. See
Figure 15.
4.
Measure the distance from the field wiring junction box to
the condensate pump, and cut two 18 AWG or larger wires
to correct length and strip the insulation at both ends of
each wire. See Figure 15.
5.
Connect these two wires to the two wires on the water
heater using wire nuts or other connectors.
6.
Connect the free ends of the two wires to the shut off
switch on the condensate
pump in accordance
with the
manufacturers
recommendations.
7.
Turn on electrical power to the water heater.
8.
Press the power button to turn the water heater on and
select the desired operational mode. After about 8 minutes,
the heat pump will turn on.
9.
Test the operation of the shut off switch by unplugging the
condensate pump and filling the condensate reservoir with
water until the float switch opens the circuit.
10. The heat pump should turn off and the error code "HEAT
PUMP FAULT" wilt appear on the user interface screen.
11. Plug the condensate
pump in and verify that the pump
operates
and pumps the water out of the condensate
reservoir.
12. The error on the user interface should clear and the heat
pump should operate after 8 minutes.
S
CirreC_t r
ILl
i L2
_40v
s...
1 Phase
Power supply
Ground
Wire
1
Electrical
Service ground
FIGURE
14.
14