Unit Dimensions − Inches (mm)
A
SIDE VIEW
Model Numbers
−018
24−1/4 (616)
−024
24−1/4 (616)
−030
24−1/4 (616)
−036
24−1/4 (616)
−042
28−1/4 (724)
−048
28−1/4 (724)
−060
28−1/4 (724)
WARNING
This product and/or the indoor unit it is matched
with may contain fiberglass wool.
Disturbing
the
insulation
maintenance, or repair will expose you to fiberglass
wool dust. Breathing this may cause lung cancer.
(Fiberglass wool is known to the State of California
to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact
your supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900

General Information

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 shows
torque values for fasteners.
506081−01 09/08
B
A
B
25−1/4 (641)
25−1/4 (641)
29−1/4 (743)
29−1/4 (743)
29−1/4 (743)
37−1/4 (925)
33−1/4 (845)
during
installation,
OUTDOOR COIL FAN
COMPRESSOR
SUCTION AND LIQUID LINE
CONNECTION
OPTIONAL UNIT STANDOFF KIT
(4) (FIELD INSTALLED)
Table 1. Torque Requirements
Parts
Service valve cap
Sheet metal screws
Machine screws #10
Compressor bolts
Gauge port seal cap
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold
gauge set that features low loss anti−blow back fittings.
See figure 1 for a typical manifold gauge connection setup.
Manifold gauge sets used with HFC−410A refrigerant
systems must be capable of handling the higher system
operating pressures. The gauges should be rated for use
with pressures of 0 − 800 on the high side and a low side of
30" vacuum to 250 psi with dampened speed to 500 psi.
Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
Only use Allen wrenches of sufficient hardness
(50Rc − Rockwell Harness Scale minimum). Fully
insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9
ft−lbs for small valves, to 25 ft−lbs for large valves) to
prevent refrigerant loss during shipping and
handling. Using an Allen wrench rated at less than
50Rc risks rounding or breaking off the wrench, or
stripping the valve stem recess.
The liquid and suction line service valves are used for
removing refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Page 2
A
DISCHARGE AIR
SIDE VIEW
Recommended Torque
8 ft.− lb.
11 NM
16 in.− lb.
2 NM
28 in.− lb.
3 NM
90 in.− lb.
10 NM
8 ft.− lb.
11 NM
IMPORTANT