CAREFULLY READ THIS ENTIRE MANUAL IN ITS ENTIRETY PRIOR TO BEGINNING ANY
INSTALLATION PROCEDURES.
1. In order to ensure valid warranty, a qualified and licensed gas fitter must install
this heater.
2. The heater must be hung in such a fashion so as to conform with the clearances
to combustibles described on the nameplate of the heater, and any local or
applicable codes.
3. The heater may be used in public garages provided the installation conforms to
all local and national codes for the installation of gas burning appliances.
Heaters must be installed a minimum of eight feet above the floor. Minimum safe
distances to combustibles must be maintained. When installed over hoists, the
minimum required safe distances to combustibles must be maintained from the
uppermost point of the combustible material placed on the hoist.
It must be located with respect to building construction and equipment so as to
4.
provide sufficient clearances and accessibility for servicing.
Where there is the possibility of exposure to combustible airborne materials or vapour,
consult the local Fire inspector's office, the fire insurance carrier or other applicable
authorities for approval of the proposed installation.
DO NOT USE IN AN ATMOSPHERE CONTAINING
HALOGENATED HYDROCARBONS OR OTHER CORROSIVE
CHEMICALS. SOME COMPOUNDS IN THE ENVIRONMENT CAN CAUSE AN
ACCELERATED RATE OF CORROSION TO THE HEAT EXCHANGER.
1. Only persons trained and experienced in gas supply piping should be engaged to
install the supply piping to the heaters. All gas piping must be in accordance with
all national and applicable codes on the installation of gas appliances. Gas
supply piping must be sized so as to provide adequate gas supply and pressures
as indicated on page 3 of this installation manual.
2. A 1/8" NPT (3.2mm) plugged tapping, accessible for test gauge connection, must
be installed immediately upstream of the gas supply connection to the heater.
Consideration must be given to the fact that this heater will expand and contract
3.
during the heating cycles and care must be taken so as not to cause stress on
the gas supply piping system. A suitably approved flexible gas connector must
be used to connect the heater to the rigid gas supply piping, and it must be
connected so as to provide free movement without causing stress on the flexible
gas connector or the rigid piping.
This heater is equipped with an automatic ignition system.
There is no pilot. No person shall attempt to light the heater by hand.
Serious injury, property damage or death may occur.

GENERAL INSTALLATION PROCEDURES

HAZARDOUS LOCATIONS

GAS SUPPLY

WARNING