For Left Rear Piping - LG TMNC092DYAA Service Manual

Multi type air conditioner
Table of Contents

Advertisement

• Bundle the piping and drain hose together by wrapping
them with vinyl tape for enough to cover where they fit into
the rear piping housing section.
Wrap with vinyl tape
Pipe
Drain hose

For left rear piping

Route the indoor tubing and the drain hose to
the required piping hole position.
Insert the piping, drain hose, and the connect-
ing cable into the piping hole.
Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection later.
Tape the drain hose and the connecting cable.
• Connecting cable
Indoor unit installation
• Hang the indoor unit from the hooks at the top of the instal-
lation plate.
• Insert the spacer etc. between the indoor unit and the
installation plate and separate the bottom of the indoor unit
from the wall.
Indoor unit
Installation plate
8cm
44 Multi Air Conditioner
Vinyl tape(wide)
Connecting cable
Drain pipe
Spacer
Flaring work and connection of piping
Connecting the pipings to the indoor unit and
the drain hose to drain pipe.
• Align the center of the pipes and sufficiently tighten the
flare nut by hand.
Indoor unit tubing
• Tighten the flare nut with a wrench.
Wrench
Indoor unit tubing
Outside diameter
mm
Ø6.35
Ø9.52
Ø12.7
Ø15.88
Ø19.05
• When extending the drain hose at the indoor unit, install the
drain pipe.
Drain hose
Adhesive
Wrap the insulation material around the con-
necting portion.
• Overlap the connection pipe heat insulation and the indoor
unit pipe heat insulation material. Bind them together with
vinyl tape so that there is no gap.
Plastic bands Insulation material
Flare nut
Pipes
Open-end wrench (fixed)
Flare nut
Connection pipe
Torque
kg . m
inch
1/4
1.8
3/8
4.2
1/2
5.5
5/8
6.6
3/4
6.6
Indoor unit drain hose
Vinyl tape
(narrow)

Advertisement

Table of Contents
loading