4. Trouble Shooting
Display
Title
code
Max. C/T
22
I Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
Yes
Is compressor
Wire connection
condition normal?
Yes
Is inverter PCB assembly
power connection normal?
Yes
Is input voltage normal?
Yes
Is inverter PCB assembly
normal?
Yes
Recheck power and installation condition
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
Input Over Current
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
No
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
¡ Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
1.083~1.123Ω ±5%
No
2. Check insulation resistance between compressor
terminal and pipe (over 50MΩ )
¡ Replace compressor if abnormality found
1. Check inverter PCB assembly U,V,W connector
connection condition
No
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
¡ Reassemble if abnormality found
Check connection between inverter PCB assembly and
No
bridge diode(misconnection, disconnection)
¡ wiring again if abnormality found
Check
No
R~S/S~T/T~R phase voltage is 380V ±10%
R~N/S~N/T~N phase voltage is 220V ±10%
¡ Check connection condition and wiring if power is
abnormal.
No
Check inverter PCB assembly IPM normality
¡ Replace inverter PCB assembly
- 108 -
Check point & Normal condition
1. Malfunction of Compressor
2. Blocking of Pipe
3. Low Voltage Input
4. Refrigerant, Pipe length, Blocked...