Multi Air Conditioner
SVC MANUAL(General)
MODEL : Multi-Inverter Type
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.

Advertisement

Table of Contents
loading

Summary of Contents for LG Multi-Inverter Type

  • Page 1 Internal Use Only http://biz.lgservice.com Multi Air Conditioner SVC MANUAL(General) MODEL : Multi-Inverter Type CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
  • Page 2: Table Of Contents

    1. Self-diagnosis Function ..................41 2. Pump Down ......................43 3. Evacuation......................44 4. Gas Charging .......................45 5. Cycle Part ......................46 6. Electronic Parts....................47 - 1 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 3: Part 1 General Information

    Part 1 General Information 1. Safety Precautions ......................3 2. Model Line Up ........................6 3. Nomenclature........................7 - 2 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 4: Safety Precautions

    Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug. There is risk of fire or electrical shock. - 3 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 5 Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred. - 4 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 6 Check the drainage of the indoor unit after the repair. If drainage is faulty the water to enter the room and wet floor. - 5 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 7: Model Line Up

    No. of connectable indoor units Max.2 Max.3 Max.4 Max.4 Total capacity index of connectable indoor units Power supply 1Ø, 208~230V, 60Hz Chassis - 6 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 8: Nomenclature

    Indicates that this is multi system outdoor unit using R410A Ex) A2U : Connectable max. 2 indoor units A4U : Connectable max. 4 indoor units - 7 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 9: Part 2 Functions & Controls

    6.4 Child Lock Function.....................22 6.5 Forced operation ......................22 6.6 Sleep Timer Operation ....................23 6.7 Timer(On/Off) ......................23 6.8 Defrost Control (Heating) ....................23 - 8 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 10: List Of Functions & Controls

    Wireless LCD remote control General central controller General central controller Optional CAC network (Non LGAP) function Dry contact Optional Dry contact - 9 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 11 Soft start for compressor Optional Test function Test operation Notes: The Exploded View part has the particular Function table for each model. - 10 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 12: List Of Functions

    Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. - 11 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 13: Air Flow

    Mode7 Mode6 Mode5 Mode4 Mode3 7~8° Mode2 OPEN NOTE: Some Models are different by swing width and swing pattern. - 12 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 14: Air Flow Step

    After one minute, it is opposite. Vane 1 Vane 3 Vane 4 • Comparison of Air Flow Types 4-Open (conventional) Swirl Swing (New) - 13 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 15: Air Purifying

    Dust electrode discharge Dust particles Photo-Catalyst Coated Mesh Ionizer +4.8KV discharge Polluted Air Purified fresh Air Generating plasma Odour Odour molecule - 14 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 16: Installation Functions

    • The central control could operate inappropriately depends on indoor unit type, when the remote controller is set as slave. - 15 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 17: How To Set E.s.p

    ❈ The E.S.P value is set at the proper value at the factory. So it is highly recommended that you should not change the E.S.P value at your discretion. - 16 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 18: High Ceiling Operation

    Selection of speed can be done by slide switch at the back of the LCD wired remote. installation on the higher ceiling Installation on the normal-height ceiling - 17 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 19: Reliability

    Compressor OFF Temp. ➔ Setting Temp-1°F(0.5°C) • In 10-min dehumidification operation, the indoor fan operates with the low airflow speed. - 18 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 20: Convenience Functions & Controls

    Setting step 13~14 minutes 1 minute 2~3 minutes (Cooling Only) Unit Operation Indoor Setting step L Low Comp. Setting step - 19 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 21: Auto Operation (Fuzzy Operation)

    • While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidifica- tion operation. - 20 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 22: Auto Restart Operation

    Memorized condition are on / off condition, operating mode (cooling/ heating), set temperature and fan speed. The unit will memorize the above conditions and start with same memorized condition. - 21 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 23: Child Lock Function

    - The operation will be started if the ON/OFF button is pressed. - If you want to stop operation, re-press the button. - 22 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 24: Sleep Timer Operation

    • The second defrost starts only when the outdoor pipe temperature falls below – 6°C after from ending of the first defrost and more than 4 minutes operation of compressor. - 23 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 25: Part 3 Control Logic

    7. Defrost Control .........................31 8. LEV Control........................32 9. Oil restoration operation....................34 10. Compressor warm-up control logic................34 11. Heat sink control......................35 - 24 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 26: Compressor

    Frequency → Number of poles BLDC Motor IPM (Inverter) U V W X Y Z Position Detect (16Bits) Circuit - 25 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 27: Step(Frequency) Control

    ✽ The compressor get the minimum step in case Step base value is lower than the minimum step of operating capacity. - 26 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 28: Reversing Valve Operation

    7. If the compressor is stopped during heating mode by Thermistor signal, reversing valve will remain in heating position. - 27 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 29: Discharge Pipe Control

    T1:90 (Option)˚C Hz(Option) COMP Hz (Option) Down Down 10 pulse 10 pulse Expansion valve Stop control (Option) up (Option) up - 28 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 30: Input Current Control

    5 Hz 5 Hz Frequency Setting Frequency Frequency Setting Frequency (Option) (Option) frequency fixed fixed frequency fixed [Hz] Down Down - 29 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 31: Outdoor Fan Control

    26°C 45°C 22°C 41°C 18°C 38°C 14°C 28°C 24°C 10°C 18°C 4°C 14°C 0°C -4°C 9°C 2°C -8°C -3°C - 30 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 32: Defrost Control

    Indoor defrost signal OFF indoor unit on/ Starting maximum defrosting time count Reversing Valve start Indoor Fan ON/OFF Outdoor Fan - 31 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 33: Lev Control

    Comp (Reset) Open Close -200 time Starting Time constant Initializin Starting control control control Heating and cooling Heating Cooling - 32 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 34 2. When the temperature reaches 4˚C, system return to the starting control pulse value. Pull open Starting LEV Target Pulse opening Target step Time (Option) Comp starting Time(sec) - 33 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 35: Oil Restoration Operation

    Opening target : 0.7 300 sec. 0 sec. 0 sec. 0 sec. 180 sec. 90 sec. Time (option) Time (option) Time (option) - 34 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 36: Heat Sink Control

    Heat Sink temp Toff=85(Option)˚C T2=75 (Option)˚C T1=70 (Option)˚C 5 Hz 5 Hz COMP Hz (Option) (Option) frequency frequency frequency Down Down - 35 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 37: Part 4 Test Run

    4. Test Run 1. Check before Test Run.....................37 2. Test Run Flow chart ......................38 3. Test Running ........................39 - 36 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 38: Check Before Test Run

    2.0 MΩ as a result of refrigerant accumulation in the internal compressor. If the insulation resistance is less than 2.0 MΩ, turn on the main power supply. - 37 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 39: Test Run Flow Chart

    Guide Normal • Each indoor unit should be tested. • If the unit has accessory, it should be tested. - 38 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 40: Test Runing

    ❏ Aren't terminal screws loosened? (refrigerant and drain piping)? ❏ Is there any leakage of refrigerant? M4..118N.cm{12kgf.cm} M5..196N.cm{20kgf.cm} M6..245N.cm{25kgf.cm} M8..588N.cm{60kgf.cm} - 39 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 41: Part 5 Trouble Shooting Guide

    1. Self-diagnosis Function....................41 2. Pump Down........................43 3. Evacuation ........................44 4. Gas Charging ........................45 5. Cycle Part ........................46 6. Electronic Parts ......................47 - 40 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 42: Self-Diagnosis Function

    Communcation error between in and out Indoor Out-Piping sensor error Differnt mode operation EEPROM Check Sum Error Indoor BLDC Fan Lock - 41 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 43 Outdoor BLDC Fan Lock Outdoor Fan is not operating 7times ◑ 3times ◑ PFC Fault Error(S/W) Over Current of Outdoor Unit PFC - 42 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 44: Pump Down

    – Open the low-pressure valve on the charge set slightly to air purge from the charge hose. (5) Set the 2-way valve to the closed position. - 43 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 45: Evacuation

    (4) Disconnect the charge hose from the vacuum pump. – Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted, replenish as needed. - 44 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 46: Gas Charging

    1 minute and then repeat the procedure (pumping down-pin). - 45 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 47: Cycle Part

    2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty. - 46 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 48: Electronic Parts

    4) Replace P.C.B Ass'y 5) IC01A(KIA7036) 5) The voltage of micom pin 19 5) Replace P.C.B Ass'y : DC4.5V↑ - 47 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 49 * Check display P.C.B Assembly - Voltage between CN-DISP1 should be DC +5V, - If problem still persists, Replace display PCB - 48 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 50 Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor. - 49 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 51: When Indoor Fan Does Not Operate

    The voltage of Pin No 1(orange) and 3(black) of CN-FAN. About AC 160V over About AC 50V over SSR is not damaged Check SSR - 50 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 52: When The Louver Does Not Operate

    If there are no problems after above checks. • Confirm the assembly condition that are catching and interfering parts in the link of the vertical louver - 51 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 53: Troubleshooting Indoor Error

    8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. → Repair or Change the PCB. - 52 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 54 3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) → Repair or Change the main PCB. 4. Check the installation of wired remote controller. (Noise interference) → Adjust the state of installation - 53 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 55 3. Check the level of water 4. Check the volt. Of Drain pump power supply. (AC 230V) → Repair or Change the main PCB. - 54 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 56 Press the on/off button or mode change button and matching the indoor unit mode same as the first operated indoor unit - 55 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 57 2. If the EEPROM value & the Program value are not matched, the Code is Displayed 3. After Checking the connection and Insertion, replace the PCB or Option PCB - 56 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 58 → Check Red line to Black line, Blue line to Black line → The resistance should infinite → replace the motor - 57 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 59: Troubleshooting Outdoor Error

    • 24k/36k 1. In Case of CH53, Check the Connection → L , N at the ter- minal block - 58 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 60 Resistance(Ω) at 20°C Constant Inverter Terminal comp. comp. Ω U-GND 2MΩ 2MΩ V-GND 2MΩ 2MΩ W-GND 2MΩ 2MΩ - 59 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 61 In case that the control box is opend and before checking electrical parts, it should be checked that the LED 01M, 02M turned off(wait 7 minutes after main power OFF), otherwise it may cause electrical shock. - 60 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 62 Check inverter PCB assembly IPM normality Is inverter PCB assembly → Replace inverter PCB assembly normal? Recheck power and installation condition - 61 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 63 - Check output the CT Sensor : DC 2.5±0.2V < Input Power Source Check Point > < Main PCB> <CT Sensing Check Point> - 62 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 64 Power connection normal? Inverter PCB assembly CN(L), CN(N) Replace inverter PCB assembly Is Inverter PCB Normal? Recheck power and installation condition - 63 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 65 < Input Power Source Check Point > < Main PCB> <DC_LINK Sensing Check Point> <DC Link Voltage Check Point> - 64 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 66 LGMV similar as Replace high pressure sensor at manifold gauge? Check pipe is blocked or not and take measure - 65 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 67 2. Check short or not at the connector of high pressure switch (Normal open) < Main PCB : Connection Check Point > < Checking the Press switch > - 66 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 68 1. Check the Input Voltage (L–N ➔ 220V±10%) 2. Check Input Voltage Sensor output voltage (2.5Vdc±10%) < Input Power Source Check Point > - 67 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 69 5. Trouble Shooting < Input Voltage Sensing Check Point > < Inverter PCB> INPUT(V) - 68 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 70 Check inverter PCB assembly IPM normality Is inverter PCB assembly normal? → Replace inverter PCB assembly Recheck power and installation condition - 69 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 71 ③ Replace PCB assembly if it is short between pins Signal pin Signal pin Signal pin except No.4,5 pins. CAUTION PFCM module No.4,5 pins are internal short state. - 70 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 72 Power connection normal? Inverter PCB assembly CN(L), CN(N) Is Inverter PCB Normal? Replace inverter PCB assembly Recheck power and installation condition - 71 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 73 < Input Power Source Check Point > < Main PCB> <DC_LINK Sensing Check Point> <DC Link Voltage Check Point> - 72 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 74 Check inverter PCB assembly IPM normality Is inverter PCB assembly → Replace inverter PCB assembly normal? Recheck power and installation condition - 73 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 75 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerant. - 74 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 76 1. Check the Input Voltage (L–N ➔ 220V±10%) 2. Check Input Voltage Sensor output voltage (2.5Vdc±10%) < Input Power Source Check Point > - 75 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 77 Is transmission cable Re-connect transmission cable connected correctly? Is MAIN PCB normal? Replace MAIN PCB Replace inverter compressor PCB - 76 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 78 3. If the resistance of the sensor is 0 kΩ or ∞, then sensor is abnormal. If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal. Ω - 77 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 79 Max. single indoor unit Model Gross max. capacity capacity A2UW183FA2 A3UW243FA2 A4UW363FA1 A4UW363FA2 Check Point 1. Check the indoor unit capacity. - 78 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 80 Recheck power and installation condition Check Point - Check the EEPROM Check sum & Direction <EEPROM Direction Check Point> <MAIN PCB> - 79 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 81 Check Point - Check the install condition for over load. (Refrigerant, Pipe length, Blocked, …) - 80 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 82 2. Check resistance between No.24 pin and NO.25 pin of PCB PFC module - only 48/56k 3. Resistance value should be in 7kΩ ±10%.(at 25°C). PFCM : Measuring resistance between No.19,20 pin - 81 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 83 4. Check the PFC Module No.19, 20 and IPM Module No.24, 25 pin soldering condition. PFCM : Measuring resistance between No.19,20 pin - 82 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 84 2. Voltage vaule should be in 1V ±0.2V. Check voltage betwen 1pin and 4pin of fan motor Fan motor connector Tester <Main PCB> - 83 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 85 Is inverter PCB assembly Check inverter PCB assembly IPM normality normal? → Replace inverter PCB assembly Recheck power and installation condition - 84 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 86 5. Trouble Shooting < Main PCB wiring Check Point > < Input Power Source Check Point > - 85 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 87 NOVEMBER, 2010 P/NO : MFL63744402...