Oil Tank; Piping Installation; Electrical Connections - Nordyne 04MD-091A-12-FA Installation, Operation And Maintenance Manual

Oil fired warm air furnaces (down-flow or horizontal model)
Hide thumbs Also See for 04MD-091A-12-FA:
Table of Contents

Advertisement

Table
3:
Minimum
Chimney
Base
Temperatures
(°F)
Chimney Height (ft.)
Nozzle
Chimney Thermal Resistance < R6
0.50
300
1400
535
725
0.65
275
1340
430
535
0.70
270
1330
405
505
0.75
260
1320
380
475
0.85
250
1300
355
430
1.00
225
1300
365
430
Chimney Height (ft.)
Nozzle
_
Chimney Thermal Resistance > R6
0.50
0.65
0.70
0.75
0.85
1.00
< - less than,
185
200
220
250
175
185
205
220
175
185
195
215
175
185
195
210
165
185
195
205
165
185
195
205
>-greaterthan
OIL TANK
Oil storage tanks must be selected and
installed
in compliance
with applicable
codes; in the United States, NFPA 31,
Standard for the Installation
of Off Burn-
ing Equipment,
Chapter 2. and in Can-
ada, CAN/CSA-B139,
Installation
Code
for Oil Burning
Equipment,
Section 6.
Observe all local codes and by-laws.
In general, the oil tank must be properly
supported
and remain
stable
in both
empty and full condition.
The oil tank
must be fitted with vent and supply pipes
to the outdoors.
Refer
to the above-
mentioned
codes
for sizing.
The vent
pipe must be no tess than 1¼ inches
I.P.S., and terminate with an appropriate
vent cap in a location where it will not be
blocked. The fill pipe must be no less
than 2 inches I.P.S., and terminate with
an appropriate
cap in a location where
debris will not enter the fill pipe during oil
delivery.
If located indoors, the tank should nor-
mally
be in the lowest
level,
(cellar,
basement,
etc.).
It must be equipped
with a shut-off valve at the tank outlet
used for the oil supply. The oil tank must
be located as to not block the furnace /
room exit pathway.
Observe
all clear-
ances specified
in the above-mentioned
codes.
PIPING INSTALLATION
In the United States, NFPA 31, Standard
for the Installation of Oil Burning Equip-
ment, Chapter 2.
In Canada, the entire fuel system should
be installed in accordance
with the re-
quirements of CAN/CSA B139, and local
regulations.
Use only approved
fuel oil
tanks piping, fittings and oil filters.
Ensure that all fittings used in a copper
oil line system are high quality flare fit-
tings. Do not use compression fittings.
Do not use Teflon tape on any fittings.
Pressurized
or gravity feed installations
must
not exceed
3 PSIG.
Pressures
greater than 10 PSlG may cause dam-
age to the shaft seal. If the height of the
oil stored in a tank above the oil burner
exceeds 11½ feet, it may be necessary
to use a pressure-regulating
device ap-
proved for this purpose.
The furnace may be installed with a one-
pipe system with gravity feed or lift. The
maximum allowable
lift on a single line
system is 8 feet. Lift should be measured
from the bottom (outlet) of the tank, to
the inlet of the burner. Sizing a single
line system is complex because of the
difficulty
estimating
the pressure
drop
through each fitting, bend and compo-
nent in the line. In general, keep single
line
systems
short
as
possible.
The
following
chart shows the allowable line
lengths (horizontal
+ vertical) for single
and two-line oil piping systems. All dis-
tances are in feet.
Table
4: Oil Lines
Copper Tubing Oil Line Length (Feet)
Single-Pipe OD
Two-Pipe OD
In retrofit applications,
where an existing
oil line system
is in place,
a vacuum
check wilt help determine the efficacy of
the existing oil line system The vacuum
in a system should not exceed 6" Hg. for
a single pipe system, nor 12" Hg. for a
two-pipe system.
NOTE: The oil burner requires the use of
a bypass
plug when
converting
from
single-pipe
to two-pipe
oil piping
sys-
tems. See burner manufacturer's
instruc-
tions.
All fuel systems
should
include
an oil
filter between
the fuel oil storage tank
and the oil burner. For best results, in-
stall the oil filter as close to the burner as
possible. When using an indoor oil tank,
the oil filter may be installed at the tank
downstream
from the shut-off valve. If
firing
the furnace
under the 0.65 gph
rate, a 7 to 10 micron line filter should be
installed
as close to the oil burner as
possible.
ELECTRICAL
CONNECTIONS
The furnace
is listed by the Canadian
Standards
Association
(CSA). It is fac-
tory
wired
and
requires
minimal
field
wiring.
In the United States, the wiring
must be in accordance with the National
Fire
Protection
Association
NFPA-70,
National Electrical
Code, and with local
codes and regulations.
In Canada,
all
field wiring should conform to CAN/CSA
C22.1 Canadian Electrical Code, Part 1,
and by local codes, where they prevail.
The furnace should be wired to a sepa-
rate and dedicated
circuit in the main

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

04md-140a-16-fa

Table of Contents