2.1. Making the unit ready for operation 1. Connect the plug to the mains supply. VALLOX DIGIT2 SE is now ready for operation. 2. Turn the unit on and choose a suitable ventilation power at the control panel. There Humidity sensor are either one or more control panels.
+16…+20 °C. 2.4. Ventilation control with carbon dioxide sensor (option) • In carbon dioxide control, VALLOX DIGIT2 SE adjusts fan speed so as to keep carbon dioxide content in the ventilation zone below the setpoint. When two or more sensors are used, fan speed is adjusted according to the highest measuring result.
INSTRUCTIONS FOR USE 2.6. Ventilation control with voltage or current signal • VALLOX DIGIT2 SE fan power can be controlled with a voltage or current signal coming from remote monitoring. • The signal can be used to select speeds 0 to 8. However, if carbon dioxide or humidity adjustment is enabled, the maximum fan speed cannot be exceeded.
• In other fault situations, the contacts are closed. 2.18. Air filtering VALLOX DIGIT2 SE has an F7 class fine filter (B) and a G3 class coarse filter (A) on the supply air side as well as a G3 class coarse filter (C) on the extract air side.
3.3.13. Controlling the direct-current fan on extract air side (does not apply to VALLOX DIGIT2 SE as it has an AC fan) The desired adjustment value for the direct current fan is selected with the + and – buttons. The DC fan exhaust rotation speed of the extract air fan can be decreased by decreasing the percentage.
Page 11
3.3.14. Controlling the direct-current fan on supply air side (does not apply to VALLOX DIGIT2 SE as it has an AC fan) The desired adjustment value for the direct current fan is selected with the + and – buttons. The DC fan - supply rotation speed of the supply air fan can be lowered by decreasing the percentage value.