Outdoor Air Temperature Control - Panasonic CS-RE9HKE Service Manual

Hide thumbs Also See for CS-RE9HKE:
Table of Contents

Advertisement

13.2.2 Freeze Prevention Control
1 .Frequency of the compressor
For prevention of freezing of the indoor evaporator, the frequency of the
compressor will be changed according to the indoor piping temperature.
2 .Indoor Fan Control
Indoor fan speed changes according to the indoor fan speed.
13.2.3 Dew Prevention Control
• To prevent dew formation at indoor unit discharge area.
• This control starts if all conditions continue for 20 minutes:
- Operated with Cooling or Soft Dry Mode.
- Indoor intake temperature is between 255
- Outdoor air temperature is less than 305 .
- Quiet Lo fan speed.
• This control stopped then receive air swing change signal from Remote Control.
13.2.4 Overload Protection For Cooling Operation
The frequency for the compressor will change according to the outdoor piping temperature.

13.3 Outdoor Air Temperature Control

13.3.1 Indoor Fan Control
1. Indoor fan is controlled by the indoor piping temperature.
Manual Fan Speed
Piping Temperature( )
and 295 .
34