Only Compressor Does Not Operate - Toshiba RAS-10SA-E-1 Service Manual

Air conditioner split wall type
Table of Contents

Advertisement

9-3-4. Only Compressor does not Operate

Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Does the OPERATION lamp flash?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 1 - 2 ) 220/230/240 VAC?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) 220/230/240 VAC?
YES
Are all the cords for compressor normal?
YES
Is the compressor motor winding normal?
(Check the winding resistor.)
YES
Is the capacitor for compressor normal?
YES
Is the overload relay normal?
YES
Does the compressor start?
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
YES
Compressor is defective
NO
See "Power can not be turned on".
NO
See "Power can not be turned on".
NO
Relays (RY01, RY02)
or IC31 or IC30 is failure.
NO
Correct cabling between indoor
and outdoor units.
NO
Cables between indoor and
outdoor units are defective.
NO
Re-wire or replace the defective cords.
NO
Compressor is defective.
NO
Capacitor is defective.
NO
Overload relay is defective.
NO
Compressor is defective.
NO
Gas shortage (Gas leakage)
– 40 –
Replace the
PC board.