Mantels And Surrounds; Wiring; Wiring For The Optional Fan Kit - Montigo L38DF-ST Installation, Operation & Maintenance Manual

See-thru indoor gas fireplace
Hide thumbs Also See for L38DF-ST:
Table of Contents

Advertisement

L38DF-ST See-thru Indoor Gas Fireplace
WARNING!
When covering the upper metal portion of the fireplace, up to
6" (as shown, Fig.24 & Fig.25) with a non-combustible material
Please Note: The decorative facing materials may be subject to
temperatures in excess of 250° F. This should be considered
when selecting facing materials.
Mantels & Surrounds
NOTE: National Canadian Gas Association mantel test requirements
are for fire hazard prevention to combustible materials.
New technology, to meet consumer and government demands for the
wise use of energy, has prompted us to manufacture many models of
fireplaces which are hot, fuel and energy efficient.
Please be aware; temperatures over the mantel will rise above normal
room temperature and walls above fireplace may be hot to touch.
WARNING!
We recommend careful consideration be given to the effects of
elevated mantel temperatures which may be in excess of product
design, for example: candles, plastic or pictures. This can cause
melting, deformation, discoloration or premature failure of T.V.
and radio components.
Painting:
Special care is recommended by the Master Painters and Decorators
Association, when painting the fireplace surrounds, to select and apply
a quality Alkyd sealer prior to the applying of latex paints. This is
to prevent leaching of water from evaporation and causing a brownish
staining effect to paint over coats.
Drywall/ Sheetrock
Non-combustible Header
(Supplied by Montigo)
Non-Combustible
Facing Material
Figure 25. Combustible surrounds, (Both Sides Typical).
WARNING!
Do not attempt to clean glass when hot.
Do not clean glass with abrasive materials as any glass etching
may cause premature glass failure.
Do not operate this fireplace without the glass door, or with a
broken glass door.
Page 12
Installation
L38DF-ST
6" 6"

Wiring

Gas Control and Pilot Wiring
Honeywell (Q3450)
Pilot Assembly
Gas Control
Connector
Fan Plug
Receptacle
Gnd Screw
Wall Switch
Figure 26.
Wiring for the L38DF-ST-I with Honeywell gas control and pilot.

Wiring for the optional Fan Kit

All L38DF-ST fireplaces may be equipped with optional fan kits for
circulating heat into the living space.
Installations in Canada which employ the fans must be electrically
grounded in accordance with CSA C22.1 Canadian Electrical Code
Part 1 and/or Local Codes.
Installations in the USA which employ the fans must be grounded in
accordance with local codes or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70-1987.
For more information see the Fan Kit Installation Guide included with
the fan kit.
NOTE:
If any of the original wire supplied with the appliance is replaced, it
must be replaced with the same type, or its equivalent.
5/1/60 Supply
G
L1 L2
Quick Connect
Figure 27a. Wiring schematic for optional fans.
f i r e f e a t u r e
L38DF-ST-I
Pilot Electrical
Harness Connector
Honeywell Gas
Control (SV9501M)
Junction Box
Black
115VAC
24VAC
Green
40 VA
Transformer
L38DF-ST
L2-WH
G
L1-BLK
p g
lu to motor
Part No. XG0810 - 092109
White