Concealed Duct High Static Pressure
Remote controller switch monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to
acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.
1. Push
and
The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No.
is also displayed.
2. Pushing TEMP.
the following table.)
3. Pushing
temperatures of indoor units and their outdoor unit in the control group are displayed.
4. Push
button to return to the normal display.
CODE No.
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
03
04
Indoor unit fan cumulative operating
F3
buttons simultaneously for at least 4 seconds to call the service monitor mode.
buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See
(left side of the button), select an indoor unit to be monitored. The sensor
2
4
Indoor unit data
Data name
Indoor unit heat exchanger (coil)
temperature (TCJ)
Indoor unit heat exchanger (coil)
temperature (TC)
hours (x1 h)
1
3
CODE No.
60
61
62
63
Compressor suction temperature (TS)
64
65
6A
F1
– 26 –
Installation Manual
Outdoor unit data
Data name
Outdoor unit heat exchanger (coil)
temperature (TE)
Outside air temperature (TO)
Compressor discharge temperature
(TD)
Heatsink temperature (THS)
Operating current (x1/10)
Compressor cumulative operating
hours (x100h)
EN
26-EN