Front Panel (Door); Boiler Piping In Heating / Cooling Application - Viessmann Vitocrossal 200 CM2 Series Installation Instructions Manual

Gas condensing boiler with cylinder burner heating input: 663 to 1112 mbh 194 to 326 kw
Hide thumbs Also See for Vitocrossal 200 CM2 Series:
Table of Contents

Advertisement

Vitocrossal 200 CM2 Installation Instructions

Front Panel (door)

Boiler Piping in Heating / Cooling Application

Legend
A System supply
B System return
C Valve
D Flow check valve
E Circulation pump
F Automatic feed valve
G Pre-charged expansion tank
Heating /
Cooling unit
Heating /
Cooling unit
Heating /
Cooling unit
Water
Chiller
1. Screw profile studs into the threads of the front
panel (door).
2. Insert front panel retainers into the notches on the
bottom panel.
3. Tilt up the door and snap door into place.
4. Secure door with M5 screw.
The boiler, when used in connection with a refrigeration
system, must be installed so that the chilled medium is
piped in parallel to the boiler and with appropriate valves
to prevent the chilled medium from entering the boiler.
The boiler piping system of a hot water heating boiler is
connected to the heating coils located in the air handling
units. The boiler piping system may be exposed to
refrigerated air circulation and must be equipped with
flow control valves or other automatic means to prevent
gravity circulation of the boiler water during the cooling
cycle.
Check the installation instructions of the chiller
manufacturer carefully for additional requirements.
Cooling season starts: Close valve V1 and open valve V2.
Heating season starts: Close valve V2 and open valve V1.
Metal tags labelling these valves should be attached.
IMPORTANT
In the above system, the circulating pump must be
operated from a separate on/off switch - not from the
boiler control.
Boiler
27