CS-E9BKP CU-E9BKP5 / CS-E12BKP CU-E12BKP5
Panasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oy
Attached accessories
Applicable piping kit
CZ-3F5, 7AEN (E9BK)
CZ-4F5, 7, 10AN (E12BK)
SELECT THE BEST LOCATION
INDOOR UNIT
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place
where
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be
at least 2.3 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short
circuit of the discharged air.
• If piping length is over the common length, additional
refrigerant should be added as shown in the table.
noise
prevention
is taken
www.ilmalämpöpumput.com
Piping size Common
Model
Gas Liquid
E9BK
3/8"
E12BK
1/2"
Indoor/Outdoor Unit Installation Diagram
into
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
54
Max.
Max.
Length
Elevation
Piping
(m)
(m)
Length
(m)
1/4"
7.5
5
10
1/4"
7.5
5
15
Additional
Refrigerant
(g/m)
10
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-e12bkp5Cu-e9bkp5Cs-e12bkp