9-2-4. ADDITION OF REFRIGERANT
• Additional charging is not necessary if the pipe length does not exceed 30 m (100 ft).
• If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the
permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe
extensions and indoor unit have been vacuumized.
* When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit).
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have
a serious effect on operation performance.
Max. pipe
Max. height
Model
length
difference
75 m
30 m
HA30,36
245 ft
100 ft
70
30 m
33 m
37 m
40 m
43 m
100 ft
110 ft
120 ft
130 ft
140 ft
0 oz
6 oz
12 oz
18 oz
24 oz
0 kg
0.2 kg 0.4 kg 0.5 kg 0.7 kg 0.9 kg 1.0 kg 1.2 kg 1.4 kg 1.5 kg 1.7 kg 1.9 kg 2.0 kg 2.2 kg 2.3 kg 2.4 kg
Additional refrigerant charging amount
46 m
49 m
52 m
55 m
58 m
150 ft
160 ft
170 ft
180 ft
190 ft
30 oz
36 oz
42 oz
48 oz
54 oz
61 m
64 m
67 m
70 m
73 m
200 ft
210 ft
220 ft
230 ft
240 ft
60 oz
66 oz
72 oz
78 oz
84 oz
75 m
245 ft
86 oz