Section 3. Installation Instructions
14
GAS CONNECTIONS
GAS LINE INSTALLATIONS
The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that
may be used on the same meter. The gas line from the meter will usually be of a larger size than the gas valve supplied
with the heater. Therefore a reduction of the connecting gas pipe will be necessary. Make this reduction as close to the
heater as possible.
ANSIZ223.1
CSA B149.1 Natural Gas and Propane Installation Codes
A manual main shut-off valve must be installed externally to the heater.
DO NOT INSTALL THE GAS LINE UNION INSIDE THE HEATER CABINET. THIS WILL VOID YOUR WARRANTY.
SEDIMENT TRAPS
MASTERTEMP
®
125 Pool and Spa Heater Installation and User's Guide
NOTE
WARNING
National Fuel Gas Code,
18–24" of 3/4"
Manual
Gas line from
Shut-off
Valve
Valve
1" Dia. or larger
(See "Recommended
Pipe Sizes" Chart)
Bell
Reducer
At least 9"
At least 3"
Union
Sediment
Trap
Figure 6.
Rev. B 8/14