Correction Factors - Mitsubishi Electric PLA-RP·AA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PLA-RP·AA:
Table of Contents

Advertisement

7

CORRECTION FACTORS

7-1. COOLING CAPACITY CORRECTION FACTORS
Outdoor unit
5m
1.00
PUHZ-P100VHA
PUHZ-P125VHA
1.00
PUHZ-P140VHA
1.00
7-2. HEATING CAPACITY CORRECTION FACTORS
Outdoor unit
5m
PUHZ-P100VHA
1.00
PUHZ-P125VHA
1.00
PUHZ-P140VHA
1.00
Refrigerant piping length (one way)
10m
30m
20m
0.985
0.957
0.931
0.981
0.946
0.914
0.976
0.931
0.893
Refrigerant piping length (one way)
10m
30m
20m
0.997
0.991
0.985
0.997
0.991
0.985
0.997
0.991
0.985
40m
50m
55m
0.908
0.886
0.876
0.885
0.858
0.845
0.858
0.827
0.813
40m
50m
55m
0.979
0.973
0.970
0.979
0.973
0.970
0.979
0.973
0.970
42