EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 eda@electrodetectors.co.uk Email: Web: www.electrodetectors.co.uk...
EDA-Z5008 & Z5020 - Installation and Operation Manual Electro-Detectors Revision History Manual Author Software Date Description Version Version V1.00 03-06-11 First Release User Manual V1.01 19-07-11 Technical Manual Added Electro-Detectors Version ZerioPlusI&OM_V1.01 Page 2...
EDA-Z5008 & Z5020 - Installation and Operation Manual Contents / Index Introduction Front Panel Display and Keys User Operations System Normal Fault Conditions Silence the Buzzer Reset a Fault Alarm Condition Silence the Alarm Re-sound the Sounders Reset an Alarm Menu Navigation 3.10...
Page 4
EDA-Z5008 & Z5020 - Installation and Operation Manual Electro-Detectors Version ZerioPlusI&OM_V1.01 Page 4...
EDA-Z5008 & Z5020 - Installation and Operation Manual Introduction Electro Detectors has been manufacturing radio fire alarm systems since 1987 and with the introduction of a harmonised specification for Europe has now complemented its range of products to meet EN54 Part 25. Based on the popular Zerio system, it has been designed to be capable of handling 240 devices in 20 zones.
EDA-Z5008 & Z5020 - Installation and Operation Manual Front Panel Display and Keys Figure 1.1 Front Panel Display and Buttons Status Supply – This LED will be illuminated when mains is present Delays Active – Illuminated if a fire Zones In Alarm...
EDA-Z5008 & Z5020 - Installation and Operation Manual User Operation Please note: No operator serviceable parts are contained within this panel. Always refer to a qualified technician for parts and servicing. System Normal In normal operation the screen will show either the date and time, or the supplier/service contact details. If requested by the customer, the unit will be configured to alternate between the two.
EDA-Z5008 & Z5020 - Installation and Operation Manual Alarm Conditions In a fire condition, a screen similar to that below will be displayed. The Fire LEDs will flash and the appropriate zone LED(s) will flash and the system sounders will be activated (assuming the system is programmed to do this). The first two lines on the display details the first zone that has been activated, the last zone to activate, and the total number of zones in alarm.
EDA-Z5008 & Z5020 - Installation and Operation Manual 3.10 Changing the system date and time – all access levels To set the date and time, press ‘MENU’, enter the correct password, select ‘1-Setup’, ‘1- Time & Date’. Use the ←and→ keys to navigate to the value to change and the ↑...
EDA-Z5008 & Z5020 - Installation and Operation Manual 3.14 Enable a Device – all access levels To enable a previously isolated device, press ‘MENU’ and enter a valid password. Select ‘2-Disable/Enable’, select ‘2-Enable’, select ‘2- Enable Device’. Using the ↑ or ↓ keys, select the device number to be enabled and press ‘ENTER’. To enable more devices press ‘ENTER’...
EDA-Z5008 & Z5020 - Installation and Operation Manual 4. Advanced User Operations Please note: No operator serviceable parts are contained within this panel. Always refer to a qualified technician for parts and servicing. General Assuming the correct password is entered, the user can sign on as an advanced user. This allows some extra functions not available to the basic user.
Page 12
EDA-Z5008 & Z5020 - Installation and Operation Manual Select Test Mode – Advanced, Service and Commissioning users only. BS5839 and EN54 specify what tests should be performed, and at what intervals. ALWAYS FOLLOW ANY TESTING SCHEDULE OR ROUTINE RECOMMENDED BY THE SYSTEM INSTALLER. As a rough guide the system should be tested weekly, but sounders only need to be tested every month.
EDA-Z5008 & Z5020 - Installation and Operation Manual Callpoint Override – Commissioning user only When set to YES, callpoints will cause an alarm and sounders will sound if operated in Test Mode. When set to NO, callpoints will not cause sounders to sound if operated in Test Mode. With YES selected, the service engineer can perform a silent system test for detectors while leaving the callpoints active.