Connections For The 1794-Oe8H Hart Analog Output Module On A 1794-Tb3G Or 1794-Tb3Gs Terminal Base Unit - Allen-Bradley 1794-IE8H User Manual

Flex i/o hart analog modules
Table of Contents

Advertisement

Connections for the 1794-OE8H HART Analog Output Module on a
1794-TB3G or 1794-TB3GS Terminal Base Unit
Bus
Flexbus
uC
0
1
2
3
+ _
Ch0
16
17
18
19
20
+ _
Chassis
Ground
Ch4
35
36
37
34
+V -V (COM)
NC
24C dc
Supply In
+V = +24V dc = Terminals C-34 and C-50
-V = COM = C-35 and C-51
Chassis Ground = Terminals B-16, B-33, C-38, C-40...45, and C-47
NC = No connection
For daisy-chaining: Supply in - C-34 (+) and C-35 (-)
1. Connect the individual output wiring to (+) terminals (0, 4, 8, 12) on the
2. Connect the associated output to the corresponding (-) terminal (1, 5, 9,
3. Connect +V dc power to terminal 34 on the 34 to 51 row (C).
4. Connect -V to terminal 35 on the 34 to 51 row (C).
250 Ω
21.6V
HART
Modem
45 Ω
1794-OE8H Module
4
5
6
7
8
9
10
11
12
13
+ _
+ _
Ch1
Ch2
21
22
23
24
25
26
27
28
29
+ _
+ _
Ch5
Ch6
38
39
40
41
42
43
44
45
46
47
Chassis Grounds for Shields
Supply out - C-50 (+) and C-51 (-)
0 to 15 row (A) and on the 16 to 33 row (B) (terminals 17, 21, 25, 29) as
indicated in the table below.
13) on the 0 to 15 row (A), and on the 16-33 row (B) (terminals 18, 22,
26, 30) for each input as indicated in the following table.
Install Your FLEX I/O Analog Modules
+V
Power
Supply
-V
+
I
F
-
4 to 20 mA
Actuator
14
15
A
+ _
Ch3
30
31
32
33
B
+ _
Chassis
Ground
Ch7
48
49
50
51
C
+V
-V (COM)
NC
24C dc
Supply Out
(1794-TB3G shown)
Publication 1794-UM063A-EN-P - March 2006
3-11
4 to 20 mA
Valve
41441
41440

Advertisement

Table of Contents
loading

This manual is also suitable for:

1794-oe8h

Table of Contents