Thermocouple (T/C) Input Specifications:
Input
Sleeper
 Thermocouple Types B, E, J, K, N, R, S, T.
 USB Programmable Zero 0~±99% of the Span.
 USB Programmable Span Within Thermocouple Type
A
limits.
 Input Impedance 1MΩ Minimum.
 T/C Lead Resistance 100Ω Maximum.
 Cold Junction Comp. -20~90°C.
+
B
 Accuracy:
-
C
 Temperature Drift:
 CJC Error <±1°C.
GND
 Sensor Break Output Drive:
Input
Sleeper
Voltage Input Specifications:
 USB Programmable Zero 0~±99% of the Span.
 USB Programmable Span ±100mVdc to ±10Vdc and
A
 Minimum Input Resistance 300kΩ.
+
B
 mV Maximum Over-range 3Vdc Continuous.
-
C
 V Maximum Over-range 60Vdc Continuous.
 Linearity and Repeatability <±0.02% FSO Typical.
GND

Connecting Thermocouples to a Sleeper:

 E, J, K, N, T <±1°C.
 B, R, S <±2°C.
 E, J, K, N, T <±0.05°C.
 B, R, S <±0.2°C.
 Function High Upscale.
 Function Low Downscale.

Connecting Voltage Signals to a Sleeper:

Bipolar.