Z-2400-SLEEPER

Description:

The Z-2400 series of units support the communication of data signals via
a wireless network. The Sleeper provides a two universal input unit that
wakes up at a selected time interval, and sends its values through to the
Base. The Sleeper is a battery powered module, ideally suited for mobile
monitoring applications. It can also be used with a power plug pack.

Ordering Information:


Z-2400-Sleeper:
2x Universal Input Sleeper, battery or plug pack powered.

XU-USB:
USB Programming Key - for programming analogue inputs.
System Limits:
Max 32 Sleepers and/or 32 Remotes per Base.

Specifications:

Voltage
Operating temp.
RF data rate
RF frequency
RF channels
RF power
Spreading method
Modulation
Nodes
Tx range
Tx power
Rx sensitivity
Analogue Inputs
Connection Indication
Multiple Mesh use
Default Mesh ID

Software Versions:

The Z-2400 series of units require the following software versions for operation:

MicroScan V5.1 (or later) - all units.

XU Software V1.30 (or later) - for programming Sleeper analogue inputs.
The latest version of software can be downloaded via the link online at
9~36Vdc.
-40~+85°C.
250Kb/s.
2405~2485MHz.
16.
1mW.
Direct sequence.
O-QPSK.
64 nodes per mesh (1 Base, 32 Remotes and 32 Sleepers).
~100m (line of sight).
+4.5dBm in boost mode.
-100dBm in boost mode.
RTD (Pt100, Pt1000), Thermocouple (B, E, J, K, N, R, S, T), mA, V, & mV.
Toggling LEDs on start-up.
Mesh ID 0~255.
1 (1, 2, 3, 4, 5, 6, 7, 8).
3
Wireless Data Link
Modules for MicroScan.
www.intech.co.nz/downloads