5.2
Discharge resistor and protection
The discharge resistor is required to discharge the DC bus of the drive whilst changing
from one supply to the other.
Table 5-3 Discharge resistor and protection values
SP1201 to SP1202
SP1203 to SP1204
SP2201 to SP2203
SP3201 to SP3202
SP4201 to SP4203
SP1401 to SP1406
SP2401 to SP2404
SP3401 to SP3403
SP4401
SP4402 to SP4403
SP5401 to SP5402
SP6401
SP6402
SPMA1401
SPMA1402
SPMD1401
SPMD1402
SPMD1403 to SPMD1404
SP3501 to SP3507
SP5601 to SP5602
SP6601 to SP6602
SPMA1601
SPMA1602
SPMD1601
SPMD1602
SPMD1603
SPMD1604
*The chosen thermal overload relay must have a class 10 trip characteristic.
High temperatures
The discharge resistor can reach high temperatures. Locate the resistors so that
damage cannot result. Use cable having insulation capable of withstanding high
temperatures.
WARNING
32
Rdis
Drive
(Ω)
220
100
100
100
100
680
220
220
220
100
100
100
100
100
100
100
100
100
220
100
100
100
100
100
100
100
100
www.controltechniques.com
Total Power
Short term (1s)
rating
energy rating
(W)
(J)
6
3950
4
2580
6
4030
12
8670
9
6470
17
12180
6
3940
11
7720
9
6660
18
13050
25
18330
33
24510
49
36250
33
24510
49
36250
33
24510
49
36250
62
46560
12
8870
23
17210
35
25850
35
25850
35
25850
35
25850
35
25850
37
27230
37
27230
Unidrive SP Low Voltage DC Installation Guide
Thermal overload
relay trip setting
(A)*
0.13
0.25
0.34
0.48
0.48
0.1
0.25
0.32
0.3
0.6
0.79
1.0
1.1
1.0
1.1
1.0
1.1
1.1
0.35
0.8
0.9
0.9
0.9
0.9
0.9
1.0
1.1
Issue Number: 1
Need help?
Do you have a question about the Unidrive and is the answer not in the manual?
Questions and answers