SYMPTOM
Humidifier or Humidifier Control "chatters" or clicks On and
Off rapidly
TROUBLESHOOTING PROCEDURE
• Check for steady 22 VAC to 30 VAC across the "R" and "C"
terminals of the Humidifier Control with a voltmeter.
• Check, with a voltmeter, that the HVAC signal across the
"W/G" and "Cf" terminals of the Humidifier Control is a
steady 22 VAC to 30 VAC.
• Make sure that the Outdoor Temperature Sensor wiring is
not running alongside other wires carrying high voltage
(120 VAC or higher). (Automatic Mode Only)