Summary of Contents for socomec SUNSYS H50

  • Page 1 SUNSYS H50 Installations- und bedienungsanleitung Manual de instalación y uso Manuel d’installation et d’utilisation Installation and operating manual Manuale di installazione e uso...
  • Page 2 Warranty on products in the SUNSYS H series Sicon S.r.l., which is part of the SOCOMEC group with registered headquarters at Via Sila 1/3 – Z. I. Scovizze, 36033 Isola Vicentina (Vicenza), guarantees that its SUNSYS H series products are compliant with technical specifications and applicable quality standards.
  • Page 3 SOCOMEC retains full and exclusive ownership rights over this document. Only a personal right to use the document for the appli- cation indicated by SOCOMEC is granted to the recipient of the document. The reproduction, modification or disclosure of this document, either entirely or partially and by whatever means, is expressly prohibited except with the prior written consent of Socomec.
  • Page 5: Table Of Contents

    11. TECHNICAL SPECIFICATIONS ..........28 SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 6: General Information

    1. GENERAL INFORMATION This user manual specifies installation and maintenance procedures, technical data and safety instructions for SOCOMEC solar inverters. For further information visit the Socomec website: www.socomec.com. Any work carried out on the equipment must be performed by skilled, qualified technicians.
  • Page 7: Unpacking

    Documentation Nut and washer for inverter mounting A N D I O N N U A L A T T A L I N G I N S R A T O P E SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 8: Identification Data Plate

    2 GENERAL INFORMATION 2.3. IDENTIFICATION DATA PLATE 2.3-1 Model Technical data Serial number SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 9: Description

    3. DESCRIPTION 3.1. GENERAL DESCRIPTION OF COMPONENTS 3.1-1 LCD display and control panel Input connection Output connection Communication port SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 10: Installation

    • of a suitable size; • clean; • free from inflammable items; • not exposed directly to sunlight; • maintained at a temperature between -18 °C and 40 °C. 4.2. CONDITIONS FOR INSTALLATION 4.2-1 SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 11: Wall Fixing

    INSTALLATION 4.2-2 Suitable installation clearances 50 cm 50 cm 30 cm 30 cm 30 cm 50 cm 50 cm 4.3. WALL FIXING 4.3-1 5 viti M6 3 viti M6 4 viti M6 SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 12: Connections

    Check that the input and output cables of the photovoltaic system are clearly identified. 5.1. DESCRIPTION 5.1-1 PV module inputs AC output, with External PE Ground DC = 2 strings in parallel connections communication connection L1, N, and PE interface SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 13 Connecting the PV system to positive or negative earth DC distribution panel (GND+ or GND-) Photovoltaic panels A transformer must be installed Isolating transformer Load Inverter 1 Ph +N 1 Ph +N 230 Vac 230 Vac SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 14: Ac Connection

    • Check that the connection cable used matches the specifications in the table. Sizing of DC cables Model Max current Cross-section SUNSYS-H50 17.5 ADC 4 mm DC connections are divided into positive and negative poles. 5.3-1 BLACK SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 15: Communication Module Connections

    The RS-485 function enables connection of the inverter in parallel. 5.4.3-1 PIN Layout Data Format PIN FUNCTION Baud Rate: 9600 DATA - Data bits: 8 RS485/USB DATA + Stop bit: 1 RS485/RS232 Parity: N/A 12 Vdc SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 16: Commissioning

    6.3. FIRST START-UP Check that the AC, DC and communication connections are made and secured correctly. WARNING! If the country setting is wrong SOCOMEC must be contacted for assistance. 1. Power up the inverter (AC or DC) 2. Set the country.
  • Page 17 SEL and ENT are pressed simultaneously > 35 sec. Normal Normal Ground option Next Enter Normal Negative Next Enter Disable Next Enter Positive Next Enter Language English Next Enter Italian Italian Language Italian Next Enter Exit Exit Inverter SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 18: Control Panel

    ALARM LCD display SELECT ENTER Confirm Move to next menu LED indicator Condition Green LED Red LED Countdown FLASHING On grid Error or Fault Standby or night-time (no DC supply) FW update FLASHING FLASHING SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 19: Menu

    PV array voltage, current and power 5.9A 1894W Today DC Today input energy 7500Wh AC life energy Output AC energy production from installation 1450kWh DC life energy PV array DC energy production from installation 1540kWh SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 20 Event log Event List Enter 01 : Grid freq under rating 02 : Grid volt under rating 03 : empty 16 : empty Clear Event Logs Push ENT button to cancel Exit the event log SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 21: Settings

    Setting ID simultaneously ID = XX ? > 3 sec. SEL is pressed > 2 sec. Setting ID Setting ID ID = XX+1 ? ID = XX+10 ? 8.2.1-2 Local setting Country Language Insulated mode SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 22 8. MENU 8.2.1-3 Local command only for Italy as country Comando locale non attivo Non attivo Attivo Non attivo Sei sicuro Exit Comando locale Attivo SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 23: Self-Test

    UL:195.5/195.5 V Pass 415/400 ms 3 sec FH:51.50/51.50 V Pass 1004/1000ms 3 sec FL:47.50/47.50 V Pass 4009/4000ms Startup procedure 3 sec UH:253.0/253.0 V Pass 3015/3000ms 3 sec UH:192.0/192.0 V Pass 215/200 ms 3 sec SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 24: Messages

    1) AC voltage lower than nominal 1) Check the grid frequency value E28: Slow Under 2) Country configuration or grid setting incorrect 2) Check the country/frequency limits setting Voltage Range 3) Measuring circuit failure 3) Contact the technician SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 25: Fault Messages

    2) Contact the technician 1) Output relays faulty 1) Contact the technician A29: Relay Open 2) Internal control circuits not working 2) Contact the technician 3) Grid voltage measurements abnormal 3) Compare machine and grid measurement values SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 26 1. Check all switching device in boost 2. Driver for boost is defective A70: DC Curr 2. Check the driver curcuit for boost inside the Transient Over inverter 3. Check input current detection circuit 3. Input current detection circuit malfunction SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 27: Removal Of Inverter

    Once these steps have been completed, remove the nut and washer on the lower part of the inverter than remove the inverter by sliding it up from the bracket. 10.1-1 Italy self test view SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 28: Technical Specifications

    MPPT Rated current 17.5 A System information / communication LCD alphanumeric display, (16 x 2 caracters) Data logger with 10 year capacity User interface and real time clock 30 events External communication RS-485 connection SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 29 VDE 0126 A1; VDE AR-N 4105; UTE C 15-712-1; CEI-021 Immunity EN 61000-6-2 IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 Immunity SURGE IEC 61000-4-5 IEC 61000-4-6 PFMF IEC 61000-4-8 EN 60950, Draft IEC62109 -1& -2 * Disable reactive power control SUNSYS H50 - Ref.: IOMSUNHMXX05-GB 00...
  • Page 30 SOCOMEC GROUP S.A. SOCOMEC capital 11 302 300 € - R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex SOCOMEC Strasbourg 11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE Tel.