Separately Sold Parts
• Separation distance of the exhaust top
The separation distance (mm) of the exhaust pipe opening from building parts finished with
combustible material, flame retardant material, or quasi-noncombustible material shall be as shown
in Figure 9.
<Reference> The dimensions within the parentheses are the distances for the case where a
heat-proof board is installed and building parts are effectively finished with
non-combustible materials.
• Precautions for when using an anti-vibration frame
1) An exhaust extension can also be attached when an anti-vibration platform is used.
2) If the exhaust pipe extension is 500 mm or less and installed vertically, then there is no need to
secure the exhaust extension.
3) In other cases, secure the exhaust extension using, for instance, the fittings and the bolts/screws
of the unit top plate.
4) Refer to the example in Figure 7.
• Precautions for when installing a blow out extension duct
1) If a blow out extension duct is installed, there are cases when it is difficult to use a leg support
fitting and other fittings because of the shape to the duct. In such a case, use wire or other
suitable means and the bolts/screws of the duct and unit top plate to secure the blow out
extension.
2) For an example of using a leg support fitting, refer to Figure 10.
1. Outdoor unit related parts
Figure 9 (Separation distance of the exhaust top)
F-5
Figure 10