Specifications - Sanyo SGP-EGW190M Technical Data Manual

Gas heat pump air conditioner m2 high power excel w multi
Table of Contents

Advertisement

Outdoor unit
Model No.
External dimensions (mm)
Height
Width
Depth
Weight (kg)
Performance (kW)
Cooling capacity
Heating capacity (Standard)
Heating capacity (low temp.)
Hot Water (Cooling mode)
Power generation capacity (rating)
Generate electricity power source
Power supply specification
Electrical rating
Running amperes (A)
Cooling
Power input (kW)
Power factor (%)
Running amperes (A)
Heating
Power input (kW)
Power factor (%)
Starting amperes (A)
Gas Type
P
H
Gas Band
L
E
Gas consumption (kW)
Cooling
Heating (Standard)
Heating (low temp.)
Compressor
Cooling oil (L)
(type)
Crankcase heater (W)
Paint color (Munsell code)
Notes
1. Cooling and heating capacities in the tables are determined under the test conditions of JIS B 8627.
Operating condition
Indoor air intake
temp.
Outdoor air intake
temp.
・Effective heating requires that the outdoor air intake temperature be at least –20°CDB or –21°CWB.
2. The Generate electricity is the generating-end output. The power output externally is calculated by subtracting the
self-consumed power. Power generation output is controlled in accordance with the air conditioning load, and the
maximum power that can be generated is 4.3 kW.
3. Gas consumption is the total (high) calorific value standard.
4. Outdoor unit operating sound is measured 1 meter from the front and 1.5 meters above the floor (in an anechoic
environment). In actual installations, values are normally larger than those indicated due to ambient noise and
reflections.
5. Quantities of gas and liquid refrigerant in parentheses ( ) apply when the maximum piping length exceeds 90 meters
(equivalent length). (Reducers are available locally.)
6. Specifications are subject to change without notice.
7. The gas consumption in < > apply when generator is not running.
8. Hot water heating capacity is applicable during cooling operation as in Note 1.
SGP-EGW190M2G2W
2,248
1,800
1,000(+60)
875
56.0
63.0
67.0
22.0 (@75°C exhaust)
DC2.5 (Maximum of 4.3)
220 to 240 V, 50 Hz,
Single-phase
100/200 V, 50 Hz,
Single-phase, 3-wire
6.18
1.35
95
4.57
1.01
96
30
Propane gas (G31)
Natural gas (G20)
Natural gas (G25)
Natural gas (G20)
44.0 <38.3>
48.7 <43.0>
62.1 <56.4>
7.5 (HP-9)
30
Silky Shade (1Y8.5/0.5)
Cooling
Heating (standard)
27°C DB /19°C WB
35°CDB
7°CDB/6°CWB
Engine
Displacement (L)
Rated output (kW)
Type
Oil
Quantity (L)
Starter motor
Starter type
Engine cooling water
Quantity (L)
Concentration, Freezing
temperature
Cooling water pump rated
output (kW)
Refrigerant type, Quantity
(kg)
Air intakes
Air outlet
Piping
Refrigerant gas (mm)
Refrigerant liquid (mm)
Balance (mm)
Fuel gas
Exhaust drain (mm)
Hot water supply in/out
Operating sound dB(A)
Ventilation System
Type
3
Air flow rate (m
/min)
Rated output (kW)
Drain heater (W)
Generator
Capacity (kW)
Heating (low temp.) Heating (cold environ.)
20°C DB
< 20°C DB/15°C WB
2°CDB/1°CWB
B-4

2. Specifications

2.488
12.4
Sanyo Genuine
46
DC12V × 2.2kW
AC/DC conversion type DC
starter
27
50 V/V%, –35°C
0.16
HFC [R410A], 11.5
Front and Rear
Top
φ28.58.(brazed)
(φ31.75.) (Note 5)
φ15.88.(brazed)
(φ19.05.) (Note 5)
φ9.52.(flared)
R3/4 (Bolt, thread)
φ25 . Rubber hose (length: 200)
Rp3/4 (Nut, thread)
58
Propeller fans (×2)
380
0.70 × 2
40
4.3
< 20°C DB/15°C WB
-10°CDB/-11°CWB