④ Click the "Configure..." button.
⑤ Make the settings shown in the following figure, and then click the "OK" button. When you return to the screen in
step ①, click "Apply".
A
B
C
D
E
F
No.
Item
A Enable all notifications
Seconds between power
B
failure and first notification
Seconds between subsequent
C
power failure notifications
Minutes on battery before
D
critical alarm
When the alarm occurs, run
E
this program
F Next, instruct the computer to
Click Configure...
Check this if you want to display all warning messages related to power failures.
Specifies the time between a power failure and the first warning message.
No warning message appears if power is restored within the specified time.
Specifies the interval between subsequent warning messages.
Specifies the number of minutes that should elapse after a power failure until the OS
shutdown begins.
The minimum time is 2 minutes. The OS shutdown begins after the specified time,
or after the battery power becomes low (as specified in step ③), whichever occurs
earlier.
Check this check box and enter a command file name if you want to execute a
command file before starting the shutdown. Only commands which finish executing
within 30 seconds can be entered here.
Specifies whether Windows 2000/XP/Server 2003 should shut down or hibernate.
If you select "Shut Down", Windows2000/XP/server2003 is shut down.
If you select "Hibernate", all of the contents of memory are copied to hard disk.
"Hibernate" cannot be selected unless the "Enable hibernation" check box is checked
in the "Hibernate" tab.
This completes the settings.