⑤ Set MAIN MCCB
to "OFF."
Buzzer: Beep-beep, beep-beep, beep-beep...
- BATTERY
****
⑥ Set MAIN MCCB
to "ON."
After 5 seconds elapse, the state becomes as shown below.
Buzzer: Stopped
- ONLINE
****
When the UPS is working properly, the buzzer sound, LCD display, and LED state will be as
indicated in steps ⑤ and ⑥.
When the power outage simulation test does not finish properly
Check the possible causes and counter measures in the table below, and then conduct the power outage
simulation test again from step ①.
Possible Cause
Are both battery packs installed properly?
Is the forced bypass switch
set to the "Bypass" side?
Forced Bypass
Is "Green OUTPUT" off?
Are "Red ALARM" and "Red WARNING" on?
Contact your supplier or SANYO DENKI when "Red ALARM" and "Red WARNING" are on or when the
UPS does not operate properly even if you perform the corresponding countermeasure above.
⑦ Check that the UPS operates properly.
Green: Blinking Green:Lit Red:Off
Green: Lit Green: Off
Check that two battery packs and b
bracket
⇒ See No. ③ and ④ in §5.1 "UPS" to confirm position
of the battery packs and b
Set the switch to the "Inverter" side.
⇒Step ⑥ of §6.2 "Attaching LCD Panel"
Perform the ON operation properly.
⇒Steps ② and ③ of §7.3 "Power Outage Simulation
Test"
Contact your supplier or SANYO DENKI.
This completes the power outage simulation test.
⑤ Set this to "OFF."
Green: Lit
Red: Off
⑥ Set this to "ON"
Green: Lit
Countermeasure
are installed properly.
attery pack securing bracket.
Preparation Before Operation
Green: Blinking
Green: Lit
Red: Off
Green: Lit
Green: Lit
Red: Off
attery pack securing
26