Pipe Checking Operation (Auto Addressing Mode); Automated Checking Of Pipe Connection (Auto Addressing Option); Apply The Power To The Outdoor Unit - Samsung MH026FNCA Service Manual

Free joint multi air conditioner
Hide thumbs Also See for MH026FNCA:
Table of Contents

Advertisement

2.2. Apply the power to the outdoor unit.

Outdoor unit will try to communicate the number of indoor units specified by SW01 on outdoor display PCB.
Does LED show "Normal display"?
"Normal display" means, right 2 digit of
LED on Display PCB displays '00' and
left 2 digit of LED displays indoor unit
Is error code started with ''
Check the indoor unit, outdoor unit or wiring
according the error code table.
2.

Pipe Checking Operation (Auto Addressing Mode)

Automated checking of pipe connection (Auto addressing option)

• Turn on the outdoor unit and wait for one minute.
During these 60 seconds,the left display DIS01 will show sequentially
00-01-02-03-...15-00.
• E199 is showed on the display PCB of outdoor unit.
-It means you didn't do "Pipe check operation "
• Push [K1 ] button on the display PCB of outdoor unit once, then begins to start "Pipe check operation "
with displaying as
below.2.
Display
[DIS 01 ] is flickering on the setting time.
32˚F or more
Time duration
(Cool mode)
5min~10min
Samsung Electronics
Yes
address number.
No
No
''
displayed on the LED?
Yes
Button [K1] 1 times
DIS 01
DIS 02
Outdoor Temperature
less than 32˚F
(Heat mode)
20min~50min
OK : This number is displayed
only while communicating,
so each number is displayed
for a short time in order.
Nothing is displayed on the LED.
Check the power source,
power cable & FUSE on
the outdoor unit.
Troubleshooting
9-3