Installation
To accommodate both types of cabling, the RuggedMC
visible on the front panel as shown in Table 2. This switch will allow for the proper connection
regardless of the cable type configuration.
When connecting to end devices, the X-over switch should be selected to reflect the type of cabling
used. (i.e. Straight through is selected when using straight through cabling, X-over is selected
when using crossover cabling)
X-Over Position
UP
DOWN
Table 2 - X-over switch positioning for Straight through and Crossover cabling
The presence of an active LINK LED indicates that the X-over selection switch is in the proper
position.
Figure 6: Location of X-over Switch on RuggedMC
NOTE: For substation applications it is not recommended to use these ports to interface to
field devices across distances which could produce high levels of ground potential rise
(GPR), (i.e. greater than 2500V) during line-to-ground fault conditions.
RuggedCom
®
Crossover cabling is used to connect to end devices.
Straight-through cabling is used to connect to end devices.
TM
11
contains a crossover selection switch
TM