INSTALLATION ExAMPLES (CONT'D)
DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and ExHAUST AIR STREAM to the FURNACE COLD AIR RETURN

SIMPLIFIED INSTALLATION

(GOOD)
(RETURN/RETURN METHOD)
1. Furnace blower must operate when ventilation from HRV is required. The fur-
nace should be set to run continuously or interlocked with HRV. See page 15.
2. A minimum separation of 1m (39'') is recommended between the two
direct connections.
3. In order to prevent exhausting any fresh air, the HRV's exhaust air connection
should be upstream of the HRV's supply air connection when ducting to the
furnace's cold air return.
4. Due to the difference in pressure between the HRV and the equipment it is
being connected to the HRV's airflow must be balanced on site, using the
procedure found in the section "AIRFLOW BALANCING"
HRV/ furnace for Simplified Installation – Option 1
Fresh air from
Outside
Stale air to
outside
Stale air from inside
outside
* Unit airflow should be balanced while HRV is on
"High" speed and furnace blower is running.
Suggested installation for:
- When bathroom and kitchen already have lo-
cal exhaust system
- May be suitable for retrofitting
Benefits: Most cost effective installation type
Fresh air to
living areas
1 m (3' 3")
min.
recom-
mended
Cold air
return
7