Hitachi RAC-08CH8 Installation Manual page 2

Split indoor/outdoor unit
Hide thumbs Also See for RAC-08CH8:

Advertisement

G
Mount the outdoor unit on stable ground to prevent vibration and
increase of noise level.
Decide the location for piping after sorting out the different types of
G
pipe available.
Procedure to remove the
cover of wiring terminals
G
Remove the screw (1
piece).
Please face this side (suction side)
G
Hold the projected
of the unit to the wall
part at the lower left
of the cover and push
the cover upwards to
remove it.
G
To close the cover,
Hook
insert the upper part
of the cover into the
body of outdoor unit,
then be sure that the
hook below the cover
is plugged in before
screwing.
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensed
water to exhaust.
In order to flow condensed water to the drain, the unit is installed on a
stand or a block so that the unit is 100mm above the ground as shown
figure. Join the drain pipe to one hole.
At first insert one portion of the hook to the base (Portion A), then pull the
drain pipe in the direction shown by the arrow while inserting the hook
into the base. After installation, check whether the drain pipe cling to the
base firmly.
A
BASE
DRAIN PIPE
Bush
10
When using in cold region, etc.
In cold region with severe cold climate and heavy snow, water
discharged from heat exchanger freeze on the base surface and this
may affect drainage. In such a region, remove bush on the bottom face
of outdoor unit for better drainage. When using drainpipe, consult our
dealer.
For RAC-14CH8 only
G
Please mount the Outdoor unit on stable ground to prevent vibration
and increase of noise level.
Decide the location for piping after sorting out the different types of
G
pipe available.
When removing side cover, please pull the handle after undoing the
G
hook by pulling it downward.
Please face this side (suction
side) of the unit to the wall.
Please remove side cover
when connecting the piping
and connecting cord.
Pull downward
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensed
water to exhaust.
In order to flow condensed water to the drain, the unit is installed on a
stand or a block so that the unit is 100mm above the ground as shown
figure. Join the drain pipe to one hole.
At first insert one portion of the hook to the base (Portion A), then pull
the drain pipe in the direction shown by the arrow while inserting the
hook into the base. After installation, check whether the drain pipe cling
to the base firmly.
A
BASE
DRAIN PIPE
11
BUSH
When using in cold region, etc.
In cold region with severe cold climate and heavy snow, water
discharged from heat exchanger freeze on the base surface and this
may affect drainage. In such a region, remove bush on the bottom face
of outdoor unit for better drainage. When using drainpipe, consult our
dealer.
1
Insulation And Maintenance Of Pipe Connection
The connected terminals should be completely sealed with
G
heat insulator and then tied up with rubber strap.
G
Please tie the pipe and power line together with vinyl tape as
shown in the figure showing the installation of Indoor and
Outdoor units. Then fix their position with holders.
G
To enchance the heat insulation and to prevent water
condensation, please cover the outdoor part of the drain hose
and pipe with insulation pipe.
Completely seal any gap with putty.
G
Insulation material for pipe connection
Sleeve of
protection pipe
Putty
Putty
3
Power Source And Operation Test
Power Source
CAUTION
!
G
Please use a new socket. Accident may occur due to the use of old
socket because of poor contact.
G
Please plug in and then remove the plug for 2 – 3 times. This is to
ensure that the plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the
G
plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
G
<
>
IA321: A
1
Preparation of Pipe
Use a pipe cutter to cut the copper pipe.
G
G
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper
G
chips from entering the pipe.
G
Before flaring, please put on the flare nut.
Please remove
Die
the cover for
wire connection.
Outer
Diameter (mm)
6.35
9.52
12.70
2
Pipe Connection
In case of removing flare nut of an Indoor unit, first remove a nut
!
CAUTION
of small diameter side, or a seal cap of big diameter side will fly
out. Prevent water from entering into the piping when working.
Please be careful when bending the copper pipe.
G
G
Screw in manually while adjusting the center. After that, use of torque wrench to
tighten the connection.
Flare nut
Drain Pipe
9
Wrench
Torque
wrench
WARNING
!
Procedures of Wiring
In case that power is supplied from Indoor Unit
Indoor Unit
Line Cord
L
N
A
AC 220-240V
Power line
30mm
10mm
Indoor
10mm
Unit
70mm
25mm
Outdoor
10mm
Unit
10mm
GRN + YEL
35mm
The naked part of the wire core should be 10 mm and fix
G
it to the terminal tightly. Then try to pull the individual wire
to check if the contact is tight. Improper insertion may
burn the terminal.
Be sure to use only power cables approved from the
G
authorities in your country. For example in Germany: Cable
type: NYM 3x1.5mm
12
BUSH
G
Please refer to the installation manual for wire connection
9
DRAIN PIPE
to the terminals of the units. The cabling must meet the
standards of electrical installation.
There is an AC voltage drop between the L and N terminals
G
if power is on. Therefore, before servicing, be sure to
remove the plug from the AC outlet or switch off the main
switch.
Do not make any connection in the middle of the connecting
G
cable. It may cause the wire overheating, emit smoke and
fire.
2
Installation Of Remote Controller
G
The remote controller can be placed in its holder which is
fixed on wall or beam.
To operate the remote controller at its holder, please ensure
G
that the unit can receive signal transmitted from the controller
at the place where the holder is to be fixed. The unit will beep
when signal is received from the remote controller. The signal
transmission is weaken by the fluorescent light. Therefore,
during the installation of the remote control holder, please
switch on the light, even during day time, to determine the
mounting location of the holder.
The controller must
be hooked onto the
hook at the lower
Screw (2 pieces)
part of the holder.
Push in the remote
controller in the
direction as shown
in figure below.
Remote
Controller
Operation Test
G
Please ensure that the air conditioner is in normal
operating condition during the operation test.
G
Explain to your customer the proper operation
procedures as described in the user's manual.
Trimming tool
Copper pipe
CAUTION
!
Die
A
G
Please use exclusive
tool
Copper pipe
A (mm)
For R410A tool
For R22 tool
0.0
~
0.5mm
1.0mm
~
0.0
0.5mm
1.0mm
~
0.0
0.5mm
1.0mm
Outer
Torque N·m
dia.of pipe
(kgf · cm)
Small dia. side
6.35 (1/4")
13.7 – 18.6 (140 – 190)
Large dia. side
9.52 (3/8")
34.3 – 44.1 (350 – 450)
12.7 (1/2")
44.1 – 53.9 (450 – 550)
Valve
Small dia. side
6.35 (1/4")
19.6 – 24.5 (200 ~ 250)
head cap
Large dia. side
9.52 (3/8")
19.6 – 24.5 (200 ~ 250)
12.7 (1/2")
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
Valve core cap
Wiring Of The Indoor Unit
G
THIS APPLIANCE
For wire connection of the Indoor unit, you need to remove low
MUST BE EARTHED.
G
cover and front cover.
Method to remove front cover.
G
Refer to "FINAL STAGE OF INSTALLATION – How to Remove The
Front Cover".
Outdoor Unit
B
C
D
A
B
C
D
Pull the cover at 1 and 2 in the directions as shown by
G
2.0
arrows to remove the cover.
Connecting Cord
1.6 or 2.0
Control line
30mm
10mm
Wiring of The Outdoor Unit
GRN + YEL
G
Please remove the side cover for wire connection.
Strip wires
25mm
!
10mm
WARNING
WARNING
!
Checking for the electric source
and the voltage range
Before installation, the power source must be checked and
G
necessary wiring work must be completed. To make the wiring
capacity proper, use the wire gauges list below for the lead-in from
a pole transformer and for the wiring from a switch board of fuse
2
.
box to the main switch and outdoor unit in consideration of the
locked rotor current.
IMPORTANT
Cable length
up to 16m
up to 15m
up to 25m
How to Remove The Front Cover
1 Remove the front panel.
G
Please remove and attach the front panel by both hands.
G
After opening the front panel by both hands.
1
Undo the right arm while pushing it inside.
2
Slide the front panel to right as shown in figure. Then
remove while pulling it to front.
2 Remove the filters.
3 After removing two screws, pull the center of the front
cover towards you and release the claws.
Holder for
4 Pull the side faces (lower sections) of the front cover
Remote Controller
towards you as shown in the figure and remove the
cover.
3
Removal Of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap
of valve core. Then, connect the charge
hose. Remove the cap of valve head.
1
Connect the vacuum pump adapter to
the vacuum pump and connect the
charge hose to the adapter.
Fully tighten the "Hi" shuttle of the
manifold valve and completely unscrew
the "Lo" shuttle. Run the vacuum pump
2
for about 10–15 minutes, then completely
tighten the "Lo" shuttle and switch off
the vacuum pump.
Completely unscrew the spindle of the
service valve (at 2 places) in anti-
3
clockwise direction to allow the flow of
coolant (using Hexagonal Wrench key).
Remove the charge hose and tighten the
cap of valve head. Check the cap's
4
periphery if there is any gas leakage.
The task is then completed.
Gas Leakage Inspection
Please use gas leakage detector to check if leakage
occurs at the connection of Flare nut as shown on
the right.
If gas leakage occurs, further tighten the connection
to stop leakage.
Method to remove the low cover
G
If you cannot attach the side cover due to the
connecting cord, press the connecting cord in
direction to the front panel to fix it.
G
Be sure that the hooks of the side cover is fixed
in certainly. Otherwise water leakage may occur
and this causes short circuit or faults.
G
The connecting cord should not touch to service
valve and pipes. (It becomes high temperature
in heating operation.)
Wire cross-section
1.6mm
2
2.5mm
2
4.0mm
2
How to Attach the Front Cover
1
Check that the drain pan is securely attached.
2
After installing the front cover onto the unit, hook three
claws at upper side of the cover securely. Then, push the
center of the front cover to lock the claws.
3
Tighten the two screws.
4
Install the filter.
5
Slide the shafts of the right and left arms on the washable
panel along the steps to insert the shafts into the holes till
they stop. After checking that the shafts are securely
inserted, close the panel.
When the meter reaches - 101KPa
(-76cmHg) during pumping, fully
tighten the shuttle.
Meter showing pressure
Closed
Lo
Hi
Manifold valve
Charge hose
Valve
Vacuum
Valve
pump
Vacuum pump
adapter
When pumping starts, slightly loosen the
flare nut to check of air sucked in. Then
tighten the flare nut.
The body of
service valve
Cap of
valve core
Hexagonal
Wrench Key
Cap of valve head
Cap of valve head
After remove the screw
and cover, and put the
connecting cords and fix
the cover with screw.
For RAC-08/10CH8
A
B
C D
Side cover
Connection wire
is put under here
Connection wire
Screw for earth line
For RAC-14CH8 only
A
B
C D
Earth terminal
Investigate the power supply capacity and other
G
electrical conditions at the installation location.
Depending on the model of room air conditioner
to be installed, request the customer to make
arrangements for the necessary electrical work
etc.
The electrical work includes the wiring work
up the outdoor. In localities where electrical
conditions are poor, use of a voltage regulation
is recommended.
IMPORTANT
For RAC-14CH8 only
Fuse Capacity
Fuse Capacity
15A time delay fuse
10A time delay fuse
Shaft
Hole
Step