Panasonic WH-SXC09D3E5 Service Manual page 88

Air-to-water heatpump
Hide thumbs Also See for WH-SXC09D3E5:
Table of Contents

Advertisement

16.5.14. Indoor Freeze-up Protection (H99)
Malfunction Decision Conditions:
During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0 C.
Malfunction Caused:
1. Faulty water pump.
2. Insufficient water flow rate in system.
3. Water leak in system.
4. 2 way valve partially closed.
5. Clogged expansion valve or strainer.
6. Refrigerant shortage (refrigerant leakage).
7. Faulty indoor refrigerant liquid temperature sensor.
8. Faulty indoor unit PCB (main).
88

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ux09de5Wh-sxc12d6e5Wh-ux12de5

Table of Contents