Checkout & Troubleshooting - Gentex 700 SERIES Installation Instructions Manual

700 series photoelectric type single station/multi-station smoke alarms ac powered, 120v, 60hz or 220v, 50/60hz

Advertisement

HOT
BLK
1
NEUT
POWER
WHT
11
RED / YEL
10
TANDEM
7
VIO
ALARM
VIO / BLK
6
CONTACTS
BLU
3
ACCESSORY
ORN
9
ALARM
CONTACTS
YEL
4
BRN
2
BRN
5
ISOLATED
GRAY
THERMAL
8
GRAY
12
SMOKE
PLUG
ALARM
710/713 CS/CSX Wiring
CS & CSX OPTIONS
1
HOT
SMOKE ALARM
POWER
11
NEUTRAL
SWITCHED
CSX
2
HOT
OPTION ONLY
10
TANDEM
4
9
AUXILARY
CONTACTS
3
5
INTERNAL
6
JUMPER
RELAY CONTACTS
RATED LOAD RESISTIVE
0.6 AMP at 125 VAC (MAX.)
WIRING TWO OR MORE SMOKE ALARMS
OR 1 AMP at 24 VDC (MAX.)
Tandem Installation
NOTICE: ALL SMOKE ALARMS IN A TANDEM INSTALLATION MUST BE
CONTROLLED BY THE SAME FUSE OR CIRCUIT BREAKER. OTHERWISE
TANDEM UNITS WILL NOT OPERATE.
LIMITATIONS: A maximum of 12 smoke alarms ("710/713" or "720") may be connected
together. Do not exceed 125 feet between each smoke alarm. Do not exceed 1125
feet between first and last smoke alarm.
NOTICE: A MAXIMUM OF SIX (6) SMOKE ALARMS OF EITHER MODEL 710/713 OR
720 WITH THE RELAY OPTIONS (F, HF, TF, CS,CSX) MAY BE TANDEM
INTERCONNECTED.
Wire used for interconnecting shall be in accordance with article 760 of the latest
edition of the National Electrical Code (NFPA 70) and must not exceed a resistance of
10 ohms.
ELECTRICAL
AC
BOX
POWER
ELECTRICAL
BOX
TANDEM WIRE
RED / YELLOW
NEUTRAL / WHITE
HOT / BLACK
1. Run a minimum of 16 gauge, 3-conductor cable, plus ground (4 wires) to the first
junction box from a power supply and between all smoke alarms that are to be
connected together. Use ANSI/UL Listed Class 1 wire. Power limited cable for
multiple tandem connections are available at many commercial electrical retail
stores.
2. Make wire connections to the supplied plug-in connector as follows: black to black,
white to white, 3rd conductor to the red/yellow wire. The red/yellow wire should be
stripped to make the connection. Connect ground wire between metal outlet boxes.
CAUTION
RED/YELLOW wire to be capped
when not in use. This wire is for
tandem connection only. Do not
connect to any other circuit.
RATED LOAD RESISTIVE
1.0 AMP @ 24VDC MAX
0.6 AMP @ 125VAC MAX
0.56 AMP @ 220VAC MAX
CSX OPTION ONLY
CSX SMOKE ALARM
BLACK
WHITE
GRAY
RED/
YELLOW
EXTERNAL RELAY
ACTIVATES
YELLOW
SMOKE ALARM
STROBE ONLY
ORANGE
BLUE
BROWN
BROWN
TO EXISTING
SIGNALING CIRCUIT
120 VAC
QUICK DISCONNECT
TYPE PLUG
LIMITATIONS
Maximum of 12 smoke
SMOKE
alarms may be connected
ALARM
together. Do not exceed
125 feet between each
smoke alarm. Do not
exceed 1125 feet between
the first and last smoke
alarm.
SMOKE
ALARM
TO ADDITIONAL SMOKE
ALARMS (MAX 12
ALARMS PER SYSTEM)
NOTES ON TANDEM INTERCONNECTING MODELS
DO NOT connect Gentex Smoke Alarms to other manufacturers' smoke alarms.
No more than 12 Gentex models 710/713 or 720 Series may be connected in
tandem.
No more than 6 Gentex models with relay options (710F, HF, TF, CS, CSX)/
(713F, HF, TF, CS, CSX) or 720F Series may be connected in tandem.
All units connected in tandem MUST get their power from the same circuit, that is,
all smoke alarms in tandem must be controlled by the same fuse or circuit breaker.
After installation to verify proper working conditions all horns must sound in this
system.
CAUTION: Failure to observe any of the conditions set forth may cause system
malfunction and damage to the smoke alarm.
NOTICE: LOSS OF ELECTRICAL INPUT WILL CAUSE THE SMOKE ALARM NOT
TO FUNCTION. THIS SERIES DOES NOT EMPLOY A SECONDARY POWER
SOURCE. FOR MAXIMUM SAFETY YOU SHOULD INSTALL BOTH BATTERY
OPERATED AND AC POWERED SMOKE ALARMS. IF BATTERY BACK-UP
DEVICES ARE NEEDED REFER TO GENTEX 9120 SERIES OR 7109/7139
SERIES, IF A SMOKE ALARM WITH STROBE LIGHT IS REQUIRED.
MOUNTING: PLATE & SMOKE ALARM
1. Lace the connector through the provided mounting plate and secure the plate to
the junction box so that the smoke alarm snap-in tabs are in the vertical position if
wall mounted. NOTE: Mounting plate is marked "THIS SIDE OUT" and slotted for
proper positioning.
2. Plug the wire connector into the smoke alarm base.
3. Place smoke alarm up to the mounting plate, rotating it clockwise until smoke
alarm firmly locks into place. Keep the smoke alarm parallel to mounting plate so
upper and lower tabs on plate seat correctly into smoke alarm.
CHECKOUT & TROUBLESHOOTING
1. Turn test knob to the NORMAL position and supply house power to smoke alarm.
The red indicator light should flash every 15-30 seconds, showing that smoke
alarm is operating properly.
2. If red light is not flashing or the green LED is not on:
a. Check the house current.
b. Check connector plug and wire connections. NOTE: Be sure power is turned
off before checking wire connections.
c. If power supply and wiring check out, but red light does not flash, return smoke
alarm to manufacturer. See TO RETURN A SMOKE ALARM.
d. When powering up smoke alarms in a tandem installation and all smoke alarms
sound immediately, inspect all devices for those with an illuminated indicator
light. These will be the trouble units.
3. Testing with the Test Knob:
a. Rotate test knob counter-clockwise to TEST 1 position and wait up to 20
seconds for smoke alarm to sound and visual signal to flash. If smoke alarm
does not sound after 20 seconds, return smoke alarm for service.
b. After successfully testing smoke alarm, return test knob to NORMAL (non-test)
position and wait 20 seconds for the smoke alarm to stop sounding.
550-0031
Page 7-5