Sirius Satellite Radio WH 90-110 Installation, Operation & Maintenance Manual page 30

Wall mounted condensing gas boilers
Table of Contents

Advertisement

Graph 2
b) With Qaa room temperature regulator:
The temperature curve "kt" must be selected by setting parameter 70 "HC1 curve" of the QAA73 room tem-
perature control device as described in section 14.4 "QAA73: parameters which can be set by the installation
engineer (service)".
See graph 4 for selecting the curve referred to a room temperature of 20°C.
The curve is shifted automatically on the basis of the room temperature set using the QAA73 climate con-
trol.
If the system is divided into zones, the temperature curve "kt" relating to the part of the system not control-
led by the QAA73 must be selected by setting parameter H532 as described in section 16 "setting the boiler
parameters".
Graph 4
c) With aGu.500 for control of a low temperature system:
Refer to the instructions provided with the AGU2.500 accessories for connection and control of a low tem-
perature zone.
InstructIons pErtaInInG to thE
TM = Flow temperature
Te = Composite outside temperature
Sth = Kt Curve
TM = Flow temperature
Te = Composite outside temperature
InstaLLEr
0
Graph 3
91.550.1 - GB/IE