Applications (pumps, sensor, remote control ...) have to be connected to terminal as follows (see also section
14):
APPLICATION
PRIMARY PUMP PLP
DHW PUMP PDHW
HEATING PUMP P1
DHW SENSOR TS
REMOTE CONTROL QAA73 (LOW TEMPERATURE)
ROOM THERMOSTAT
HEATING PUMP P2
3 WAY VALVE
FLOW SENSOR
Parameter changes requires (see also section 16):
pcB
paraMEtEr
H552
H553
H615
H632
Boiler
11°c Δt
kpa
Wh 90
77.32
Wh 110
75,42
Boiler
Minimum Water Flow rates
Wh 90
Wh 110
InstructIons pErtaInInG to thE
Description
Hydraulic system
KonfigHKS
KonfigAusgang
Wanfo Q8
13.3 Heat excHanger pressure drop
hydraulic resistance and Water Flow rates
15°c Δt
Lit/sec
kpa
Lit/sec
1,85
37,3
1,35
2,28
41,23
1,67
Lit/sec
0,52
0,58
InstaLLEr
TERMINAL BOARD
M1: A – B
M3: 13 – 14
M3: 11 – 12
M2: 7 – 8
M2: 1 – 2
M2: 3 – 4
CLIP IN AGU 2.500
CLIP IN AGU 2.500
CLIP IN AGU 2.500
setting parameter
H552 = 50
H553 = 12
H615 = 9
H632 = 00001111
0°c Δt
kpa
Lit/sec
25,42
1,02
23,72
1,25

0°c Δt
kpa
Lit/sec
11,23
0,68
13,42
0,83
91.550.1 - GB/IE