Mitsubishi Electric LMAP04-E Installation Manual page 12

Building air-conditioners control system, lm adapter
Table of Contents

Advertisement

Explanation of function switch
Note: Function switch setting of LM ADAPTER is different according to the management item of the
equipment connected with L
SW
Switch name
SW1-1
Function switch
of local prohibit
SW1-2
Used together with
system controller switch
SW1-3
Indoor temperature
state interval switch
SW1-4 Reset filter sign/
Select enable/
disable operation
duration
SW1-5 Function switch
of LOSSNAY
SW1-6 Single set point
mode switch
SW1-7 Function switch
of SNVT_switch
SW1-8 Select enable/
disable forced
thermo OFF
SW1-9 Indoor units
test run switch
SW1-10 LMAP collective
alarm detection
time switch
SW3-2 Initialization
switch of air
conditioner units
EPROM
(Program ID)
Neuron ID
Host CPU
Power supply LED
(LED402)
CN 40
M-NET transmission
power supply on
W
. Carefully set the system.
®
ON
ORKS
Function
ON
local prohibit effective
OFF
local prohibit invalidity
used together with system controller
ON
not used together with system controller
OFF
ON
Transmission interval
(1minutes or more)
OFF
Transmission interval
(10 minutes or more)
ON
Enable
OFF
Disable
ON
LOSSNAY is operated
®
from L
W
ON
ORKS
OFF
LOSSNAY interlocks
with the indoor unit
ON
Enable single set point mode
OFF
Enable dual set point mode
ON
SNVT Standard
OFF
Original
ON
Enable forced thermo OFF
OFF
Disable forced thermo OFF
ON
ON(test run) is transmitted
to the indoor units
OFF
OFF is transmitted and
indoor units stop test run
ON
Enable
OFF
Disable
ON
Connected cancellation
command is transmitted
to the indoor units
OFF
None
Maintenance LED
CN 41
M-NET transmission
power supply off
(Factory setting)
[ LM ADAPTER Main Circuit Board (L.B) ]
Note
Operation local prohibit nv input from
®
L
W
becomes Effective when switch is ON.
ON
ORKS
Operation local prohibit nv input from
®
L
W
becomes invalid when switch is OFF.
ON
ORKS
*number of indoor units that should
be connected is 30 or less
When "ON", the reset filter sign input and the
operation duration output are enabled.
When "OFF", the reset filter sign input and
the operation duration output are disabled.
Please turn on the switch when LOSSNAY
is operation from L
W
ON
ORKS
Please turn off the switch when LOSSNAY
interlocks with the indoor units.
When "ON", whole M-NET system operates in
single set point mode. For example, if BMS does
not support dual set point, apply this switch.
When "OFF", the LMAP is detected as a
device supports the dual set point.
When "ON", the specifications of the nv using
the SNVT_switch comply with the SNVT Standards.
When "OFF", the nv using the SNVT_switch
has original specifications.
When "ON", the forced thermo OFF nv
input/output are enabled.
When "OFF", the forced thermo OFF nv
input/output are disabled.
When "ON", the LMAP collective alarm
detection maximum time become the same
as the LMAP03U (60 minutes)
(
)
LED001 , LED002
M-NET address switch
(Factory setting: 47)
LED003 , LED004
LON transformer: FT-X1
LON LED
(LED502)
10
Factory
Set timing
setting
Before power
OFF
supply
Before power
OFF
supply
OFF
Before power
supply
OFF
Before power
supply
OFF
Before power
®
.
supply
OFF
Before power
supply
OFF
Before power
supply
OFF
Before power
supply
OFF
Always
OFF
Before power
supply
OFF
Always
Function selection switch
(Factory setting: All OFF)
CPU power supply LED
(LED009)