Circulating Air & Filters; Ductwork - Air Flow; Bottom Return Air Opening [Upflow Models ]; Filters - Read This Section Before Installing The Return Air Ductwork - Goodman GMH95 Installation Instructions Manual

Gas-fired warm air furnace
Hide thumbs Also See for GMH95:
Table of Contents

Advertisement

Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length,
3/8"
1/2"
5/8"
3/4"
Feet
10
39
92
199
329
20
26
62
131
216
30
21
50
107
181
40
19
41
90
145
50
18
37
79
131
60
16
35
72
121
80
13
29
62
104
100
11
26
55
90
125
10
24
48
81
150
9
21
43
72
200
8
19
39
66
250
8
17
36
60
*Data in accordance with NFPA pamphlet NO. 54
Propane Gas Piping Chart II
XIII. CIR
XIII. CIR
CUL
CULA A A A A TIN
CUL
XIII. CIR
XIII. CIR
XIII. CIRCUL
CUL
D
- A
F
UCTWORK
IR
LOW
Duct systems and register sizes must be properly designed for the
CFM and external static pressure rating of the furnace. Design the
ductwork in accordance with the recommended methods of "Air
Conditioning Contractors of America" Manual D.
Install the duct system in accordance with Standards of the Na-
tional Board of Fire Underwriters for the Installation of Air Condi-
tioning, Warm Air Heating and Ventilating Systems. Pamphlets No.
90A and 90B.
A closed return duct system must be used, with the return duct
connected to the furnace. NOTE: Ductwork must never be attached
to the back of the furnace. Flexible joints may be used for supply
and return connections to reduce noise transmission. To prevent
the blower from interfering with combustion air or draft when a
central return is used, a connecting duct must be installed be-
tween the unit and the utility room wall. Never us a room, closet, or
alcove as a return air chamber.
When the furnace is used in connection with a cooling unit, the
furnace should be installed in parallel with or on the upstream side
of the cooling unit to avoid condensation in the heating element.
With a parallel flow arrangement, the dampers or other means
used to control the flow of air must be adequate to prevent chilled
air from entering the furnace and, if manually operated, must be
equipped with means to prevent operation of either unit unless the
damper is in the full heat or cool position.
When the furnace is installed without a cooling coil, it is recom-
mended that a removable access panel be provided in the outlet
air duct. This opening shall be accessible when the furnace is
installed and shall be of such a size that the heat exchanger can be
viewed for visual light inspection or such that a sampling probe
can be inserted into the airstream. The access panel must be
made to prevent air leaks when the furnace is in operation.
When the furnace is heating, the temperature of the return air en-
tering the furnace must be between 55°F and 100°F.
B
R
A
O
OTTOM
ETURN
IR
PENING
The bottom return air opening on upflow models utilizes a "lance
and cut" method to remove sheet metal from the duct opening in
the base pan. To remove, simply press out the lanced sections by
hand to expose the metal strips retaining the sheet metal over the
duct opening. Using tin snips, cut the metal strips and remove the
sheet metal to free the duct flanges. Using the scribe line along
the duct flange as a guide, unfold the duct flanges around the
perimeter of the opening using a pair of seamer pliers or seamer
tongs. NOTE: Airflow area will be reduced by approximately 18% if
duct flanges are not unfolded. This could cause performance is-
sues and noise issues.
Nominal Pipe Size
Schedule 40
7/8"
1-1/8"
1/2"
3/4"
1"
1-1/4" 1-1/2"
501
935
275
567
1,071
2,205
346
630
189
393
732
1,496
277
500
152
315
590
1,212
233
427
129
267
504
1,039
198
376
114
237
448
187
340
103
217
409
155
289
89
185
346
138
255
78
162
307
122
224
69
146
275
109
202
63
132
252
100
187
54
112
209
93
172
48
100
185
TIN
TIN
G AIR & FIL
G AIR & FIL
TER
TERS S S S S
TER
TIN
TING AIR & FIL
G AIR & FIL
G AIR & FILTER
TER
[U
M
]
PFLOW
ODELS
E
DGES OF SHEET METAL HOLES MAY BE SHARP.
PRECAUTION WHEN REMOVING HOLE PLUGS.
3,307
2,299
1,858
1,559
CUT USING TIN SNIPS
913
1,417
834
1,275
724
1,066
630
976
567
866
511
787
439
665
390
590
CUT FOUR CORNERS
AFTER REMOVING SHEET
METAL
F
- R
ILTERS
EAD
R
A
D
ETURN
IR
UCTWORK
Filters must be used with this furnace. Discuss filter maintenance
with the building owner. Filters do not ship with this furnace, but
must be provided by the installer. Filters must comply with UL900
or CAN/ULCS111 standards. If the furnace is installed without fil-
ters, the warranty will be voided.
On upflow units, guide dimples locate the side return cutout
locations. Use a straight edge to scribe lines connecting the
dimples. Cut out the opening on these lines.
NOTE: An undersized opening will cause reduced airflow.
Refer to Minimum Filter Area tables to determine filter area require-
ments.
0453BXA
0703BXA
0704CXA
0904CXA
0905DXA
1155DXA
*Minimum filter area dictated by heating airflow requirement.
Permanent Minimum Filter Area (sq. in)
[Based on a 600 ft/min filter face velocity]
26
CAUTION
U
SE GLOVES AS A
PRESS OUT BY HAND
Duct Flange Cut Outs
T
S
B
I
HIS
ECTION
EFORE
NSTALLING
C O O LING AIR FLO W R EQ UIREM ENT (CFM )
600
800
1000
1200
194*
194*
240
288
---
324*
324*
324*
---
---
291*
291*
---
---
432*
432*
---
---
---
388*
---
---
---
486*
SCRIBE LINES OUTLINING
DUCT FLANGES
T
HE
1400
1600
2000
---
---
---
336
---
---
336
384
---
432*
432*
---
388*
388*
480
486*
486*
486*

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gch9

Table of Contents