Battery Charger - Lennox RGEN12 Operation Manual

Residential generator set
Hide thumbs Also See for RGEN12:
Table of Contents

Advertisement

2.7 Battery Charger

The generator set is equipped with a 6-amp
float/equalize battery charger to maintain the engine
starting battery. The charger's power cord must be
connected to a 120 VAC power source. Figure 2-5
illustrates the battery charger.
The battery charger uses an AGS 10 inline fuse. The
fuse is located in the battery lead. See Figure 2-5.
1
INDICATOR
Red:
VOLTS= 11.8- -14.0
AMPS= 5.0- -6.0
Red & Green:
VOLTS= 14.0- -14.5
AMPS= 1.5- -5.0
Green:
VOLTS= 13.0- -13.6
AMPS= 0.1- -1.5
CAUTION:
To reduce the risk of elect rical shock,
connect only to properly gr ounded outlet.
INPUT: 115 VAC 50/60Hz @ 1.6A
OUTPUT: 12 VDC @ 6 Amps
MAX. BAT.: 180 Amp Hr. Max.
DATE:
Allowable Battery Types: Lead Acid a
4
3
1. LED indicators
2. AC power cord
3. Fuse
4. Battery leads, 12 VDC
Figure 2-5 6-Amp Float/Equalize Battery Charger
2.7.1
Battery Charger Operation
Figure 2-6 illustrates the three-stage charging method.
Red and green LEDs indicate charger operation. The
chart in Figure 2-7 describes the LED indicator
operation during each stage of the charging process.
Figure 2-6 Charging Method
XP-6515 4/09
6 AMP AUTOMATIC
BATTERY CHARGER
R
C
US LISTED
BATTERY CHARGER
53AB
2608KH
nd Gel Cell
2
Display
Operating Condition
Red ON
When the red LED is on, it indicates the
Green
battery is discharged and the battery charger
OFF
is recharging at the BULK rate (stage 1).
This charging rate is 6 amps. While the red
LED is on, the voltage measured (with the
battery charger on) will be 11.8--14 volts.
If the red LED stays on for more than
24 hours, refer to Section 5.4 in this manual.
Red ON
When both the green and the red LEDs are
Green ON
on, the battery charger is charging at an
ABSORPTION rate of between 1.5 and 5
amps (stage 2). This mode of charging
gradually tops off your battery, and reduces
harmful sulfating. While both LEDs are on,
the voltage measured (with the battery
charger on) should be approximately
14.0--14.5 VDC.
If both LEDs stay on longer than 24 hours,
refer to Section 5.4 in this manual.
Red OFF
When the green LED is on, the battery
Green ON
charger is charging at a FLOAT or
MAINTENANCE rate of less than 1.5 amps
(stage 3). Your battery is now 90% charged
and ready for use. This float charging current
will gradually decrease to as low as 0.1 amps
as the battery reaches 100% charge. It will
now be kept at full charge without
overcharging.
If the green LED stays on when your battery
is known to be low, refer to Section 5.4 in this
manual.
Figure 2-7 Battery Charger LED Indicator Functions