Lennox XP21 Series Installation Instructions Manual page 44

Dave signature collection system
Table of Contents

Advertisement

System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or
defrost/dehumidification). Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then system
status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Heat Pump Control
icomfort
icomfort
icomfort
LEDs
Touch
Touch
Touch
Thermostat
Thermostat
Thermostat
DS11
DS11
DS14 Red
DS14 Red
Display
Display
Display
Green
Green
1 fast flash
Off
then pause
applicable
2 fast
Off
flashes
applicable
then pause
2 fast
On
flashes
applicable
then pause
1 fast flash
Off
then pause
applicable
2 fast
flashes
Off
applicable
then pause
2 fast
flashes
On
applicable
then pause
Moderate
Alert Code
None
Moderate
None
Alert Code
Critical Alert
None
Code 124
Critical Alert
None
Code 125
Moderate /
None
Critical Alert
Code 126
Critical Alert
None
Code 131
Critical Alert
None
Code 132
Moderate
Off
Slow flash
Alert Code
Critical Alert
Off
On
Code 411
Moderate
Alert Code
Slow flash
Off
506601−01
®
®
®
Condition
Condition
Condition
First−stage
Not
compressor
heating
Second−stage
Not
compressor
heating
Not
Defrost
First−stage
Not
compressor
cooling
Second−stage
Not
compressor
cooling
Not
Dehumidification
mode
Device
communication
105
failure
Unresponsive
device
120
Active subnet
controller missing
for 180 seconds
Hardware Failure
Internal control
communication
failure
Corrupted control
parameters
Failed flash CRC
check.
Low pressure
fault
410
Low pressure
switch lockout
High pressure
fault
412
Possible Cause(s)
Possible Cause(s)
Possible Cause(s)
These are codes that show status of operation whether the system is operating in either
in first or second stage heating or cooling operation, defrost or in the dehumidification
modes.
ALERT STATUS
Equipment is unable to communicate. Indicates numerous message errors. In most
cases errors are related to electrical noise. Make sure high voltage power is separated
from RSBus. Check for mis−wired and/or loose connections between the stat, indoor
unit and outdoor unit. Check for a high voltage source of noise close to the system.
Fault clears after communication is restored.
Usually caused by delay in outdoor unit responding to indoor unit poling.
Recycle power. Check all wiring connections. Cleared after unresponsive
device responds to any inquiry.
Equipment lost communication with the thermostat. Check four wiring connections,
ohm wires and cycle power at the thermostat. Alert stops all services and waits for
heartbeat message from thermostat (subnet controller). Cleared after valid thermostat
(subnet controller) message is received.
Hardware problem on the control. Cycle power on control. Replace if problem prevents
service and is persistent. Cleared 300 seconds after fault recovered.
Internal communication on heat pump control. Alert will clear 300 seconds after fault
has recovered.
Reconfigure the system. Replace control if heating or cooling is not available. Only
applicable in the communicating mode, not in start up. Exit from Commissioning and
Execute ´Set Factory Default mode´. Control will still operate on default parameter set-
tings.
Recycle power. If failure re−occurs, replace control. System reset is required
to recover.
Unit pressures below the lower limit. System is shut down. Clears after pressure switch
closes.
Open low pressure switch error count reached 5 strikes. Check system charge using
approach and subcooling temperatures. Reset by putting outdoor unit control in test
mode or resetting low voltage power.
Unit pressure is above the upper limit. System is shut down. Check system operating
pressures and compare to unit charging charts. Clears when pressure switch closes.
Page 44