Input Voltage and Input Frequency
Table 2-7
Universal Storage Platform VM.
•
Table 2-7: Input Voltage and Input Frequency Requirements
Frequency
60Hz ±2Hz
50Hz ±3Hz
Circuit Breakers and Plugs
The PDU plugs are appropriate for the power sources at the installation
sites:
•
For installations within the U.S., the plugs are NEMA L6 30P, rated as
30A and 250V, and have two 16A circuit breakers with 20A trip values.
•
For installations outside the U.S., the plugs are IEC 309, rated as 32A
and 250V, and have two 16A circuit breakers with 20A trip values.
Customer-Supplied Rack
This section describes the power specifications and requirements for
installing the Universal Storage Platform VM storage system in a customer-
supplied rack.
•
Figure
battery backup chassis and four disk chassis
•
Figure
battery backup chassis and up to two disk chassis
•
Figure
battery backup chassis and no disk chassis
•
Figure
chassis
•
Figure
specifications
•
Figure
•
Power Distribution Units for Customer-Supplied Rack on page 2-33
Hitachi Universal Storage Platform VM Installation Planning Guide
lists the input voltage and input frequency requirements for the
Input Voltages (AC)
200V, 208V, or 230V
200V, 220V, 230V, or 240V
2-15: Maximum configuration - control frame, additional SVP/
2-16: Primary rack configuration - control frame, additional SVP/
2-17: Primary rack configuration - control frame, additional SVP/
2-18: Secondary rack configurations - including one or two disk
2-19,
Figure
2-20: Primary rack - power connection
2-21: Connecting to universal power supply (UPS)
Installation Requirements
Conditions
Tolerance (%)
1 Phase
+6% or –8%
2 Wire + Ground
1 Phase
+6% or –8%
2 Wire + Ground
2–25