Gas - Lochinvar Power-Fin Designer's Manual

Hide thumbs Also See for Power-Fin:
Table of Contents

Advertisement

Designer's Guide / Power-fin Water Heater
Chapter 3 – Gas Supply
Lochinvar products are designed with the concept of flame control. We develop combustion
systems that tightly control the flow of air and gas to deliver a clean and efficient burn. In
Chapters 1 and 2, we showed the various methods to deliver an ample quantity of air to the
appliance. In Chapter 3, we discuss delivering a steady and reliable supply of gas to the
appliance.
The key to the gas supply is sizing the gas line properly. The Power-fin will require less than a
half a pound of pressure. The following Sizing Chart is based on less than ½ pound of pressure
or less than 14 inches of pressure. The table is derived from the ANSI Z223.1, the National Fuel
Gas Code.
Simply calculate the total linear feet of straight gas pipe. Figure each elbow as equal to five
straight feet of pipe. Working down the column that matches your pipe length, find the value
GREATER THAN the total Btu/hr input of the water heater or water heaters. This will identify the
minimum nominal iron pipe size.
Nominal
Iron
Pipe
Size
10
20
3/4"
369
256
1"
697
477
1 1/4"
1,400
974
1 1/2"
2,150
1,500
2"
4,100
2,820
2 1/2"
6,460
4,460
3"
11,200
7,900
4"
23,500
16,100
The Power-fin features a Negative-Regulation or Neg-Reg gas
combustion system. The gas is introduced upstream of the
combustion blower. As the blower draws air in, the negative
pressure on the inlet of the blower pulls the gas from the gas
valve. The gas/air mixture is pushed through the blower into the
burner. The gas/air mixture filters through the ceramic burner
mesh and is ignited by the Hot Surface Igniter.
On full fire, a crisp blue flame rises off the surface of the burner.
As demand decreases, the operating control reduces the blower
speed. The flame is reduced and touches the burner surface.
The ceramic burner material is designed to burn infra-red safely without being damaged by direct
contact of the flame. Even at this reduced Btu/hr input, the gas/air mixture is balanced to provide
clean, efficient combustion.
GAS PIPE SIZING CHART
Length of Pipe in Straight Feet
30
40
50
205
174
155
384
328
292
789
677
595
1,210
1,020
923
2,260
1,950
1,720
1,560
3,610
3,100
2,720
2,460
6,400
5,400
4,870
4,410
13,100
11,100
10,000
9,000
60
70
80
90
141
128
121
113
267
246
256
210
543
502
472
441
830
769
707
666
1,440
1,330
1,250
2,310
2,100
2,000
4,000
3,800
3,540
8,300
7,690
7,380
21
LOCHINVAR CORPORATION
300 MADDOX SIMPSON PKWY
LEBANON, TN 37090
www.lochinvar.com
100
125
150
175
106
95
86
79
200
179
164
149
410
369
333
308
636
564
513
472
1,180
1,100
974
871
1,900
1,700
1,540
1,400
3,300
3,000
2,720
2,500
6,870
6,150
5,640
5,130

Gas

200
74
138
287
441
820
1,300
2,340
4,720

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents