Warning; Receiving & Unpacking Equipment - Nortec GH Series Instaliation, User & Maintenance Manual

Gh series gas fired humidifier
Table of Contents

Advertisement

WARNING
.. Improper installation, adjustment, alteration,
service, maintenance, or use can cause carbon
monoxide poisoning, an explosion, fire, electrical
shock, or other conditions which may cause
personal injury or property damage. Consult a
qualified installer, service agency, local gas
supplier, or your distributor or branch for
information or assistance. The qualified installer
or agency must use only factory authorized and
listed kits or accessories when modifying this
product. A failure to follow this warning can
cause electrical shock, fire, personal injury, or
death.
.. Should overheating occur, or the gas fail to shut
off, shut off the manual gas valve to the appliance
before shutting off the electrical supply.
.. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas
control which has been under water.
This installation guide has been designed to
provide assistance when installing, mounting, and
sizing a GH Series humidifier. Actual on site
application may vary. Consult Technical Services or
your local NORTEC representative.
RECEIVING & UNPACKING EQUIPMENT
1. Check packing slip to ensure ALL material has
been delivered.
2.
All material shortages are to be reported to
NORTEC within 48 hours from receipt of
goods. NORTEC assumes no responsibility
for any material shortages beyond this period.
3.
Inspect shipping boxes for damage and note
on shipping waybill accordingly.
4.
After unpacking, inspect equipment for
damage and
if
damage is found, notify the
shipper promptly.
5.
All NORTEC products are shipped on an
F.O.B. factory basis. Any and all damage,
breakage or loss claims are to be made
directly to the shipping company.
Condensate
Steam
Return
II
Outlet
Figure #1
Vent Can Be From The Top
Or The Back (GH 100 only)
1
Power And
i - -
Control Wiring
i--- Water Input
Line
I---
Gas Input
Line
1:::::::=========:::±:::====l1---
Drain
PRODUCT LINE
(Gas Fired Humidifier)
B
=
BASIC (On/Off)
P
=
MODULATING
MC
=
DIGITAL CONTROLLER
c/w KEYPAD
PEAK STEAM OUTPUT 100
(lbs/hr) Normal Altitude
200
FUEL
N
=
NATURAL GAS
P
=
PROPANE GAS
DEIONIZED WATER
OPTION
HIGH ALTITUDE
400
GH
B
100
N
01
HA
....
~-------------------
MODEL GH 100 SPECIFICATIONS
ALTITUDE
FUEL
BLOWER
INPUT
ORIFICE
STEAM
MANIFOLD
AIR
SHIPPING
OPERATING
(FT)
SPEED
(BTUH)
SIZE pRILL
CAPACITY
PRESS. IN
ORIFICE
WEIGHT
WEIGHT
SI E)
(LBS/HR)
W.C.
DIAMETER
(LBS)
(LBS)
NORMAL
NATURAL
MAX
119,000
E
100
-0.2
1.062"
300
500
(0-2000)
GAS
MIN
65,000
E
50
-0.2
1.062"
HIGH
NATURAL
MAX
107,000
E
90
-0.2
1.062"
300
500
(2000-4500)
GAS
MIN
58,500
E
45
-0.2
1.062"
NORMAL
PROPANE
MAX
119,000
9
100
-0.2
1.062"
300
500
(0-2000)
(LP GAS)
MIN
65,000
9
50
-0.2
1.062"
HIGH
PROPANE
MAX
107,000
9
90
-0.2
1.062"
300
500
(2000-4500)
(LP GAS)
MIN
58,500
9
45
-0.2
1.062"
- 1 -