Checking The Manifold; Regulated Gas Pressure; Electrical Troubleshooting; Heater Does Not Come On - Natco Fire-Coil 175-400 Installation And Operation Instructions Manual

Volume water heaters
Table of Contents

Advertisement

Page 22
Suggested
Manometer
Position
Main
Line
Figure 33. Gas pressure test.
4.
Remove the 1/8 inch NPT (3.2 mm) test plug in
the shutoff valve and replace it with the 1/8 inch
NPT (3.2 mm) fitting from the manometer kit.
5.
Attach one end of the manometer hose to the
fitting on the gas valve and the other end to the
manometer.
6.
Open gas supply valve to the heater and set the
temperature control high enough to call for heat.
7.
With the main burners firing, the manometer
reading should be between 5 and 10 inches (127
and 254 mm) W.C.
5A-2. Checking the Manifold

Regulated Gas Pressure

1.
Attach a manometer (or a dry gas pressure
gauge) to heater jacket (see Figure 33).
2.
Open both columns on the manometer.
3.
Use shutoff valve, on outside of heater jacket, to
shut off all gas supply to the heater.
4.
Remove the 1/8 inch NPT (3.2 mm) test plug on
the outlet side of the gas valve, and replace it
with the 1/8 inch NPT (3.2 mm) fitting from the
manometer kit.
5.
Attach one end of the manometer hose to the
fitting on the gas valve and the other end to the
manometer.
6.
Turn on gas supply to the heater, and set the
temperature control high enough to call for heat.
7.
Turn toggle switch to ON. This should activate
the main burners.
8.
9.
10. Shut the system down following the instructions
11. Disconnect the manometer tubing from the gas
Manifold
Regulated
5B. Electrical Troubleshooting
the electrical power and control components of the
heater. Read all of these procedures before starting
repairs.
caused by something reducing water flow through the
heater, causing the protective switches in the heater
system to shut down the heater.
service and problem diagnosis of the heater and
heating system.
1.
2.
3.
4.
pull the RED wire off the transformer secondary
before removing or replacing any component or wire
connection.
If power is not disconnected, jumpering gas valve or
accidental grounding of the wire harness, or
component terminals to the heater frame or jacket
could cause the ignition control fuse to blow or may
cause the heater to fire, resulting in injury or
property damage.
1.
2.
The manometer reading should be 4 inches
(102mm) W.C. for natural gas and 9 inches
(229mm) W.C. for propane gas.
Turn the toggle switch to OFF.
found on the inside of the heater.
valve and replace the 1/8 inch NPT (3.2 mm)
fitting with the original plug.
This section describes procedures for checking
Problems with heaters not firing are usually
The following tools are required for proper
Gas pressure test kit with range from 0 to 14
inches (0 to 356 mm) W.C.
Electric meter(s) with the following ranges:
a. 0 to 500 volts VAC
b. 0 to 2000 ohms ( )
c. 0 to 20 microamps (mA)
d. 0 to 50 millivolts (mV)
Tube cleaning kit with a reamer, stainless steel
brush, speed handle, and handle extensions.
A pressure gauge and a thermometer with proper
ranges for heater operation.
5B-1. Heater Does Not Come On
Important: Disconnect power to the heater or
WARNING
Make sure the heater has been properly installed.
Make sure the pump is not airlocked, clogged or
otherwise inoperative.

Advertisement

Table of Contents
loading