3.4
MENU SET C:
Pressing the Down arrow followed by the Enter/Reset button will access the Data Logging menu set. This menu
set has three options that will display recorded data about the operation of the water heater. To access the
options, use the Up or Down buttons followed by the Enter/Reset button.
3.4.1

TOTAL HRS. RUN

The Total Hrs. Run option shows the total time that the burner in the water heater has been operating for since the
counter was last reset.
3.4.2

IGNITION ATTEMPTS

The Ignition Attempts option will show the number of times the water heater has attempted to fire since the counter
was last reset.
3.4.3

LAST 10 ERRORS

The Last 10 Errors option will show the date, time and fault description for the last ten errors that caused the boiler
the stop. The Up or Down button should be used to scroll through the errors
3.5
MENU SET E:
Pressing the Down arrow 2 times followed by the Enter/Reset button will access the Water Heater Settings menu
set. This menu set has one option; to access the option press the Enter/Reset button.
3.5.1
TANK SETPOINT
The Tank Setpoint parameter allows the setpoint of the water heater to be adjusted when a flow temperature
sensor is not used. Lochinvar Limited recommends that a flow sensor is always used with this appliance.
The setpoint should be adjusted to ensure that the water is stored at 60°C and distributed at 50°C within 1 (one)
minute at all outlets. Care is needed to avoid much higher temperatures because of the risk of scalding. At 50°C
the risk of scalding is small for most people, but the risk increases rapidly with higher temperatures and for longer
exposure times. The risk to young children and to those with a sensory or mobility loss will be greater. Where a
significant scalding risk has been identified, the use of thermostatic mixing valves on baths and showers should be
considered to reduce temperature, these need to be placed as close to the point of use as possible.
The default value is 60C. To modify the temperature setting, the
Enter/Reset button pressed to store the desired setting.
3.6

EXITING USER SETTINGS MODE

To exit the user-setting mode, the Menu/Exit button should be pressed whilst in the Main Menu screen.
Alternatively, if no button is pressed for 60 seconds, the water heater will revert to its normal operating screen.
Once this has occurred, the Enter/Reset button should be pressed to switch the unit on.
DATA LOGGING
WHR SETTINGS
Up or Down button should be used and the