10-1 AIRFLOW SETTINGS WHEN THERMOSTAT IS OFF
• Set the flow rate according to the requirement of the environment after consultation with the customer.
(As the factory setting, airflow for when cooler thermostat is off is set to SECOND CODE NO. "02", while
other settings are set to "01".) (Refer to Table 6)
Table 6
Fan operation when thermo-
stat is OFF (Cooling/Heating)
Airflow rate when cooler ther-
mostat is OFF
Airflow rate when heater
thermostat is OFF
10-2 SETTING AIR FILTER SIGN
• Remote controllers are equipped with liquid crystal display air filer signs to display the time to clean air fil-
ters.
• Change the SECOND CODE NO. according to Table 7 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to "01" for air filter contamination-light.)
Explain to the customer that filters need to be cleaned periodically to prevent clogging, and the time that is
set.
• The periodical cleaning time for the filter can be shortened depending on the usage environment.
Table 7
Setting
Air filter
contamination-light
Air filter
contamination-heavy
10-3 SETTING AIR FLOW RATE INCREASE MODE
• The set airflow rate (HH, H, and L) can be increased depending on the installation condition or customer's
request. In such a case, switch the SECOND CODE NO. as shown in Table 8.
(SECOND CODE NO. is factory set to "01" for standard.)
Table 8
Setting
Standard
Slightly increase
Increase
20
Setting
Normal
Stop
LL airflow rate
Setting airflow rate
LL airflow rate
Setting airflow rate
Spacing time of display air
filter sigh
Approx. 200 hrs.
Approx. 100 hrs.
Mode No.
13(23)
Mode No.
CODE NO.
11 (21)
12 (22)
12 (22)
are the settings when shipped from the factory.
Mode No.
10 (20)
FIRST CODE NO.
0
FIRST
SECOND
CODE NO.
01
2
02
01
6
02
01
3
02
FIRST
SECOND
CODE NO.
CODE NO.
01
0
02
SECOND CODE NO.
01
02
03
English

Advertisement

Table of Contents
loading

This manual is also suitable for:

Faq100cvebFaq-c9

Table of Contents