• Heating
Tdsh<15˚C(Option)
Dis superheating
T
<15˚C
dsh
Close LEV
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Power ON
Initialization
(Duration 90 sec)
Compressor ON
Outdoor Fan ON
Starting control
(Duration 240 sec)
On-time control
(Duration continues)
Check Dis superheating
temp.(Tdsh)
control
(T
)
dsh
≥15˚C(Option)
T
dsh
Check T
in
Back to
Main Control
Power Reset
LEV
Fully close
(set 0,-200 pulse, can
hear knocking sound)
Fully Open
Standard Initial set
pulse open
Step control (every
1 min response time)
Catch up the stagnation
Step control (every
2 min response time)
Super heat control
(T
sh
T
<1˚C
sh
Open LEV
- 69 -
Part 3 Control logic
Tdsh>15˚C(Option)
= T
–T
)
suc
pipe
≥1˚C(Option)
T
sh
Check T
in
Close LEV
LGE Internal Use Only