APPENDIX A - CONTROL MODULE
4. Central Heating (CH) modes available:
CH Mode = 0 'CH with Thermostat'
CH Mode = 1 'CH with Thermostat and Outdoor Reset'
• CH Mode = 2 'CH with Full Outdoor Reset'
M O D E : 1
CH Mode = 3 'CH with Permanent Demand'
Note:
• Once CH demand is satisfi ed (i.e. CH thermostat opens or
boiler determines its minimum fi ring rate exceeds system
heating load):
• The internal heat exchanger pump is energized anytime demand
exists regardless of Pump Mode setting or type of demand (CH or
DHW).
67
Explanation
Boiler will attempt to satisfy CH demand while CH
thermostat input is closed.
Boiler will modulate its fi ring rate to maintain CH set
point and match system heat load.
CH set point adjusted in 'Settings' submenu under 'User
Menu'
Boiler will attempt to satisfy CH demand when CH
thermostat input is closed.
Boiler will modulate its fi ring rate to maintain CH set
point and match system heat load.
CH set point calculated as function of outdoor
temperature using outdoor reset curve. See fi gure A-2
Boiler will permanently attempt to satisfy CH
demand.
CH thermostat input is ignored.
CH set point calculated as function of outdoor
temperature using outdoor reset curve. See fi gure A-2
Boiler will permanently attempt to satisfy CH
demand.
CH thermostat input is ignored.
CH set point is adjusted in 'Settings' submenu under
'User Menu'
Burner shuts off, boiler enters post purge.
CH pump continues to run for 30 seconds.
Control will wait until Anti-cycle time of 180 seconds
elapses before boiler fi res again. Prevents short-
cycling.