Rfciii Systems; Maintenance - Lennox Diplomat 10HP12 Information

Diplomat 10hp series high-efficiency residential split-system heat pump
Table of Contents

Advertisement

10HP12
OUTDOOR COIL
LIQ.
SUC.
ENTERING AIR
+ 10
+ 10
TEMPERATURE
PSIG PSIG
PSIG
65 F (TXV)
137
78
75 F (TXV)
155
79
85 F (TXV)
182
80
95 F (TXV)
210
82
105 F (TXV)
240
83
65 F (RFC III)
130
59
75 F (RFC III)
155
67
85 F (RFC III)
175
75
95 F (RFC III)
210
82
105 F (RFC III)
240
87
*
For an approved match-up the 10HP60 must be used with a TXV.
2 – RFCIII Systems
The system should not be charged at ambients below
60 _F (15_C). If charging below 60 _F (15_C) is required,
the recommended method of charging is to weigh the
refrigerant into the unit according to the total amount
shown on the unit nameplate and in table 8. For line sets
varying from 20 feet, refer to table 7 for refrigerant charge
adjustment. If ambient temperature is above 60 _F (15_C)
use the subcoooling method outlined below.
SUBCOOLING METHOD (RFCIII SYSTEMS)
(Ambient Temperature Above 60_F [16_C] )
1 – Connect gauge manifold. Connect an upright
R–22 drum to center port of gauge manifold.
2 – Operate indoor and outdoor units in cooling
mode. Allow outdoor unit to run until system
pressures stabilize.
3 – Make sure thermometer well is filled with
mineral
oil
before
temperature.
4 – Read liquid line pressure and convert to
condensing temperature using temperature/
pressure conversion chart.
Condensing temperature (read from gauges)
should be a few degrees warmer than the
liquid line temperature.
TABLE 12
SUBCOOLING METHOD––RFCIII Systems*
Indoor
Outdoor
Unit
Unit
10HP12
CB/CBH19–21
10HP18
CB/CBH19–21
10HP24
CB/CBH19–26
10HP30
CB/CBH19–31
10HP36
CB/CBH19–41
10HP36 (CAN)
CB/CBH19–41
10HP42
CB/CBH19–41
10HP48
CB19–51
*Approved matchups only
5 – Place thermometer in well and read liquid line
temperature. Table 12 shows how much
warmer the condensing temperature should be.
10HP NORMAL OPERATING PRESSURES (COOLING MODE)
10HP18
10HP24
10HP30
LIQ.
SUC.
LIQ.
SUC.
LIQ.
SUC.
+ 10
+ 10
+ 10
+ 10
+ 10
+ 10
PSIG
PSIG PSIG
PSIG PSIG
145
72
160
74
170
165
73
185
76
195
195
74
215
78
225
225
77
245
80
255
255
79
275
84
290
150
61
150
60
165
170
68
175
67
190
195
75
205
73
220
230
81
240
78
255
260
85
280
81
285
checking
liquid
Condensing Temp F Warmer
Than Liquid Line At Various
Ambients
65_F 75_F 85_F 95_F 105_F 115_F
5
5
4
1
0
13
13
13
12
6
12
12
11
9
7
12
12
10
8
6
17
15
14
11
8
18
16
15
12
9
11
10
7
6
4
11
10
8
7
5
TABLE 11
10HP36
10HP36 (CAN)
LIQ.
SUC.
LIQ.
SUC.
+ 10
+ 10
+ 10
+ 10
PSIG PSIG
PSIG
PSIG
75
175
75
175
76
77
200
76
200
77
78
227
77
230
78
80
260
79
260
79
82
295
81
295
81
62
170
61
160
62
69
205
68
190
68
74
230
73
225
70
80
265
79
255
77
84
305
82
385
81
Add refrigerant to make the liquid line
temperature cooler.
Recover refrigerant to make the liquid line
temperature warmer.
6 – When unit is properly charged liquid line
pressures should approximate table 11.
E – Oil Charge
Refer to table 4 on page 6 for factory oil charge.
V – MAINTENANCE
At the beginning of each heating or cooling season, the
system should be cleaned as follows:
A – Outdoor Unit
1 – Clean and inspect outdoor coil. (Coil may be
flushed with a water hose).
2 – Outdoor fan motor is prelubricated and sealed.
No further lubrication is required.
3 – Visually inspect all connecting lines, joints
line
and coils for evidence of oil leaks.
NOTE-If insufficient heating or cooling occurs, unit
should be gauged and refrigerant charge checked.
B – Indoor Coil
1 – Clean coil if necessary.
2 – Check connecting lines, joints and coil for
evidence of oil leaks.
3 – Check condensate line and clean if necessary.
C – Indoor Unit
1 – Clean or change filters.
2 – Check blower motor for debris. Blower motors
are prelubricated and sealed. No further
lubrication required.
0
4
3 – Adjust blower speed for cooling. Static
5
pressure drop over the coil should be checked
4
to determine the correct blower CFM. Refer to
5
6
Lennox Engineering Handbook for Static
2
Pressure and CFM tables.
2
4 – Check all wiring for loose connections.
5 – Check for correct voltage at unit.
6 – Check amp–draw on blower motor.
Unit nameplate_________Actual_________.
Page 14
10HP42
10HP48
LIQ.
SUC.
LIQ.
SUC.
+ 10
+ 10
+ 10
+ 10
PSIG
PSIG
PSIG PSIG
160
72
165
72
185
74
185
73
215
76
210
76
245
78
240
78
280
80
275
80
155
61
155
63
180
63
185
64
210
68
210
69
240
73
245
74
275
76
275
78
10HP60
LIQ.
SUC.
+ 10
+ 10
PSIG
PSIG
150
73
175
75
200
76
235
78
265
80
*
*
*
*
*
*
*
*
*
*

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents