Purge Air From Water System; Part 11 - Programming The Heater; Program Access; Program System Settings - Pioneer PHR100-55 Instruction Manual

Pioneer water heater instruction manual
Table of Contents

Advertisement

the highest and lowest fan speed. After 20 minutes, Test mode stops automatically. To exit Test Mode
manually, press
{S1}
and
HIGH FIRING RATES and LOW FIRING RATES ON ALL MODELS
Carbon Monoxide
(CO%)
Carbon Dioxide
(CO
%)
2
Table 9
BTU
100,000
130,000
160,000
199,000
Table 10
F. PURGE AIR FROM WATER SYSTEM
Disconnect the wires connected to the THERMOSTAT terminals of the field connection board. Apply
power to the appliance. The display will show the appliance water temperature. Press the
keys simultaneously and hold for 1 second. The display will begin alternating between SEP and CH, and
the central heating pump will come on. If you press
display will begin alternating between SEP and DH, and the DHW pump will come on. If the appliance is a
cascade master and you press
between SEP and Sh, and the system pump will come on. You can use the
between running each pump in the system as required to help bleed out all entrapped air. Some good
indicators that air is removed include the absence of gurgling noises in the pipes and pump operation
becoming very quiet. Press
PART 11 – PROGRAMMING THE HEATER
The control allows the installer to set system limits and the heat curve for the Heater. These system limits
should not be changed by the user. It is important to document your settings within this manual after you
program the system parameters for future reference.
A. PROGRAM ACCESS
To start, press and hold
change to |000|. Then, press and hold
decrease the number.) This is the pass code. To confirm that the pass code is correct, press and hold the
{S3}
key for 1 second. If the pass code is entered incorrectly, the controller program function will cancel
and return to normal operation. If the code is entered correctly, the control will switch off the gas valve
and purge fan while showing a solid
This first function verifies that the control will function with the SuperStor Indirect Fired Water Heater.
B. PROGRAM SYSTEM SETTINGS
Next you will have to press the {S3} key to move through each function. To increase or decrease a value,
you will need to press either the
{S2}
together for 1 second.
COMBUSTION SETTINGS
NATURAL GAS
Low
0 – 10 ppm
9% - 10 ½%
9% - 10 ½%
FAN SPEEDS
IGNITION
3000
3000
3000
3000
{S2}
again, the DHW pump will shut off, the display will begin alternating
{S1}
and
{S2}
together at any time to return the control to normal operation.
{S3}
and
{S4}
simultaneously for three seconds. You will notice the display
{S1}
until you see |925|. (If you go past |925|, you can use
- - -
in the display. The display will then show a |1| alternating to |de|.
{S1}
key or
{S2}
High
0 – 20 ppm
0 – 10 ppm
9 ½% - 11%
MIN
2000
2000
2000
2000
{S2}
again, the central heating pump will shut off, the
key to change the default values. If there is no key
PROPANE LP
Low
high
0 – 20 ppm
9 ½% - 11%
MAX
5400
6950
6850
8500
{S1}
and
{S1}
and
{S2}
keys to toggle
53
{S3}
{S2}
to

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Phr130-55Phr199-55Phr160-55